Installation continued – Garland M/MST70 MASTER SERIES HEAVY DUTY GAS FRYERS Manuel d'utilisation

Page 8

Advertising
background image

Part # Rev 1.1382677 (11/12)

Page 8

INSTALLATION Continued

Ventilation and Air Supply

One of the most important considerations is ventilation.

The fryer must be installed so that products of combustions

are removed efficiently, but so that the kitchen ventilation

system does not produce drafts that interfere with proper

burner operation. The fryer flue opening must NOT be placed

close to the intake of the exhaust fan.

The fryer must never have its flue extended in a chimney

fashion. This changes the combustion characteristics of the

fryer. This will cause the fryer to be slow to recover, frequently

cause delayed ignition, and sometimes cause pilot outage.

The ideal method of ventilating a fryer is the use of a

properly designed canopy which should extend six inches

(6”) (152mm)beyond all sides of the appliance and six feet

(6’) six inches (6”) (1981mm) from the floor.

Many operators do not realize that the finest ventilation

system will break down when it is not maintained properly.

The duct system, the hood, and the filter bank must be

cleaned on a regular basis and kept free of grease.

Adequate distances must be maintained from the flue outlet

of the fryer to the lower edge of the filter bank. Filters should

never be installed in the horizontal position. They should be

installed at an angle of 45 degrees, and a drip tray should be

located beneath the lowest edge of the filter. NFPA Standard

No.96 states that “A Minimum distance of 18” (457mm)

should be maintained between the flue outlet and the lower

edge of the grease filter.” We recommend that the MINIMUM

DISTANCE BE 24” (610mm) FROM THE FLUE OUTLET TO

THE BOTTOM EDGE OF THE FILTER WHEN THE APPLIANCE

CONSUMES MORE THAN 120,000 B.T.U. PER HOUR.

A strong exhaust fan will create a vacuum in the room, for an

exhaust system vent to work properly, replacement air must

enter the room in which the vent is located.

All gas burners and pilots need sufficient air to operate and

large objects should not be placed in front of this fryer which

would obstruct the air flow through the front. A minimum of

24” (610mm) should be provided at the front of the unit for

servicing and proper operation. Air for combustion enters

the unit below the cabinet at the base. Do not place anything

around the base or under the fryer.

Assembly Of Battery

All heavy duty batteries equipment is aligned and fitted at

the factory, from left to right and must be installed in this

order. There is a diagram provided with every heavy duty

battery. All 35M/MST Fryers and 70M/MST Fryers may be

installed to battery with other GARLAND 40 Series Ranges,

sharing common manifold connections.

A. All such units should be placed in their respective battery

position. Detach valve panels to prevent damage,

remove them from the area where the battery is being

assembled.

B. Level each unit (if a range, to the oven rack) by adjusting

the six inch (6”/152mm) legs, or where legs are not used,

adjust level with shims. Readjust legs, if required.

C. Connect units together by mating the unions at each

end of the manifold. (Adjoining units must have

matching unions, unless the union parts are of the

same specifications, a leak proof connection cannot be

assured.) Hand tighten unions at this point.

D. The units should be fastened at the rear by inserting 5/16”

bolts through the holes provided at the rear of the burner

box sides. Install washer and nut and hand tighten. Be

sure of proper unit alignment in the battery before final

tightening of these bolts or unions. Improper tightening

will cause “fanning” or “bowing” of batteried units.

The final tightening of the union should be accomplished

by using a suitable spanner wrench. If such a wrench

is not available, the GARLAND union collar has special

ridges, and a cold chisel can be driven against these

ridges to properly seat and seal the union.

E. The manifold of this unit or the manifold of which is

a part of must be equipped with a certified pressure

regulator suitable for battery application and adjustable

for an outlet pressure at the manifold as specified on the

rating place

Advertising
Ce manuel est liée aux produits suivants: