Figure 11—option de câblage ex d, Figure 12—option de câblage ex e – Det-Tronics X9800 IR Flame Detector with Pulse Output Manuel d'utilisation
Page 16
95-6555
5.1
14
A2187
TABLEAU D'ALARME INCENDIE
DÉTECTEUR X9800
ALARME
24 Vcc
+
–
NOTES SUR LE CÂBLAGE:
1. EN FONCTIONNEMENT NORMAL ET EN CAS D'ABSENCE DE DÉFAUT,
LE RELAIS DÉRANGEMENT EST EXCITÉ ET SES CONTACTS SONT NORMALEMENT FERMÉS.
2. LE RELAIS D'ALARME FEU EST NORMALEMENT DÉSACTIVÉ EN CAS D'ABSENCE DE DEFAUT.
3. DES COMMUTATEURS DE TEST Oi INDIVIDUELS (OU BIEN UN SÉLECTEUR DE DÉTECTEUR
AVEC UN COMMUTATEUR D'ACTIVATION) PEUVENT ÊTRE INSTALLÉS SUR LE TABLEAU INCENDIE.
LES COMMUTATEURS DE TEST NE SONT PAS FOURNIS.
4. SE RÉFÉRER AU CHAPITRE "CARACTÉRISTIQUES" POUR LES VALEURS DE RÉSISTANCE DE FIN DE LIGNE.
SE RÉFÉRER AU CHAPITRE "RÉSISTANCES FIN DE LIGNE" POUR LES DÉTAILS SUR L'INSTALLATION.
END OF
LINE DEVICE 4
TEST
oi3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
SORTIE
IMPULSIONS
COMMUN FEU2
N.O. FEU2
N.F. FEU2
COMMUN DÉRANGEMENT1
N.O. DÉRANGEMENT1
24 Vcc +
24 Vcc –
24 Vcc –
29
28
27
26
25
24
23
22
21
LIBRE
LIBRE
RS-485 A
RS-485 B
MAN
Oi
Figure 11—Option de Câblage Ex d
A2188
TABLEAU D'ALARME INCENDIE
DÉTECTEUR X9800
ALARME
ALARME
24 Vcc
+
–
NOTES SUR LE CÂBLAGE:
1. EN FONCTIONNEMENT NORMAL ET EN CAS D'ABSENCE DE DÉFAUT,
LE RELAIS DÉRANGEMENT EST EXCITÉ ET SES CONTACTS SONT NORMALEMENT FERMÉS.
2. LE RELAIS D'ALARME FEU EST NORMALEMENT DÉSACTIVÉ EN CAS D'ABSENCE DE DEFAUT.
3. DES COMMUTATEURS DE TEST Oi INDIVIDUELS (OU BIEN UN SÉLECTEUR DE DÉTECTEUR
AVEC UN COMMUTATEUR D'ACTIVATION) PEUVENT ÊTRE INSTALLÉS SUR LE TABLEAU INCENDIE.
LES COMMUTATEURS DE TEST NE SONT PAS FOURNIS.
4. RÉSISTANCE DE FIN DE LIGNE FOURNIE AVEC LE TABLEAU D'ALARME INCENDIE.
FIN DE
LIGNE4
TEST
oi3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
SORTIE
IMPULSIONS
COMMUN FEU2
N.O. FEU2
N.F. FEU2
COMMUN DÉRANGEMENT 1
N.O. DÉRANGEMENT1
24 Vcc +
24 Vcc –
24 Vcc –
29
28
27
26
25
24
23
22
21
LIBRE
LIBRE
RS-485 A
RS-485 B
MAN
Oi
Figure 12—Option de Câblage Ex e