2. Hood Placement:

For best smoke elimination, the lower edge of the hood should be installed 36"
above the range cooking surface. (See Figure 1).

If the hood contains any combustible materials (i.e. a wood covering), it must be
a minimum of 40" above the cooking surface.

3. Consider Make-Up Air:

Due to the high volume of ventilation air, a source of outside replacement air is
recommended. This is particularly important for tightly sealed and insulated
homes.

A qualified heating and ventilating contractor should be consulted.

Range Width

Range Top

Configuration

Minimum Recommended

Blower Capacity*

Ventilation Options

30"

4 burners

600 CFM

36” Chimney Hood w/ optional blower

30” or 36” Pro Wall Hood

30” or 36” Custom Insert w/ optional blower

42” Island Hood w/ optional blower

36"

4 burners w/ grill or

griddle

800 CFM

36” or 42” Chimney Hood w/ optional blower

36” or 42” Pro Wall Hood

36” Custom Insert w/ optional blower

42” Island Hood w/ optional blower

6 burners

900 CFM

48"

4 burners w/ grill-griddle

combo or

24” griddle

1000 CFM

48” Chimney Hood w/ optional blower

48” or 54” Pro Wall Hood

48” Custom Insert w/ optional blower

54” Island Hood w/ optional blower

6 burners w/ grill or

griddle

1100 CFM

Important Notes:

It is recommended that a Thermador Professional wall or island hood or custom insert is used with Thermador Pro-
fessional Ranges.

Refer to www.thermador.com for a complete selection of Professional Ventilation options, Blowers, and Accesso-
ries.

* For high output gas ranges (60,000 BTU or greater), the minimum of one (1) CFM of ventilation per 100 BTU is
recommended. If the range has a grill or griddle, add 200 CFM to the estimated blower capacity. Additional blower
capacity may be required for longer duct runs.

For island applications, it is recommended to use a hood width that exceeds the width of the range by 6” (overlap-
ping the range by a minimum of 3” on each end).

CFM = “cubic feet per minute” (standard blower capacity rating).