OM-212 817 Page 13

3-6. Weld Output Terminals And Selecting Cable Sizes*

Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit

Not Exceeding

100 ft (30 m) Or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Weld Output

Terminals

Welding

Amperes***

10 − 60%

Duty

Cycle

60 − 100%

Duty

Cycle

10 − 100% Duty Cycle

100

4 (20)

4 (20)

4 (20)

3 (30)

2 (35)

1 (50)

1/0 (60)

1/0 (60)

150

3 (30)

3 (30)

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95

3/0 (95)

200

3 (30)

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 4/0 (120)

250

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 2 ea. 2/0

(2x70)

2 ea. 2/0

(2x70)

Output Receptacles

+

300

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120) 2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 3/0

(2x95)

*

This chart is a general guideline and may not suit all applications. If cable overheating occurs (normally you can smell it), use next size larger

cable.

**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.

( ) = mm

2

for metric use

***Select weld cable size for pulsing application at peak amperage value.