22 Port Splitters

Publication 1747-IN516B-EN-P - October 2007

Specifications

RS-232/DF1 Port Splitter- 1747-DPS1, 1747-DPS2

Attribute

Value

1747-DPS1

1747-DPS2

Power supply requirements

100 mA @ 24V dc Class2/SEL V

100 mA @ 24V dc

Isolation

No

Yes

Controller port communication
rate and checksum

8-pin DIN, autobaud @ 19.2 Kbps
or 38.4 Kbps
auto-sum BCC or CRC

9-pin male D-shell, autobaud @
19.2 Kbps or 38.4 Kbps
auto-sum BCC or CRC

Network port communication rate
and checksum

8-pin DIN, DF1 full-duplex
19.2 Kbps/CRC

9-pin male D-shell,
6-pin Phoenix-style connector for
DH-485
configurable for DH-485, DF1
half-duplex (master or slave), DF1
full-duplex, or DF1 radio modem
networks.
The communication parameters
are also configurable.

Prog/HMI port communication rate
and checksum

9-pin male D-shell, 19.2 Kbps/CRC

9-pin male D-shell, 19.2 Kbps/CRC

Status indicators

4

4

Dimensions (HxWxD) without DIN
rail, approx.

96.8 x 50.6 x 33.3 mm
(3.81 x 1.99 x 1.31 in.)

N/A

Dimesions (HxWxD) with DIN rail,
approx.

96.8 x 50.6 x 33.3 mm
(3.81 x 1.99 x 1.31 in.)

101 x 35 x 70 mm
(3.98 x 1.38 x 2.75 in.)

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…60

o

C (32…140

o

F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

–40…85

o

C (–40…185

o

F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Advertising