Napoleon Fireplaces Grandville 42 - BGD42 Manuel d'utilisation

Page 17

Advertising
background image

W415-0777 / E / 08.26.13

17

EN

(H

T

) > (V

T

)

Simple venting configurations.

See graph to determine the required vertical rise V

T

for the

required horizontal run H

T

.

REQUIRED

VERTICAL RISE

IN FEET

(METERS) V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H

T

The shaded area within the lines represents acceptable

values for H

T

and V

T

90°

V

1

H

2

90°

90°

18.3_2B

45°

0

5

(1.5)

10

(3.1)

15

(4.6)

20

(6.1)

10 (3.1)

20 (6.1)

3 (0.9)

25

(7.6)

30

(9.1)

19 (5.8)

V

2

H

1

90°

V

1

H

2

90°

90°

45°

V

2

H

1

45°

H

3

For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:

Formula 1: H

T

< 3V

T

Formula 2: H

T

+ V

T

< 40 feet (12.2m)

Example:
V

1

= 1 FT (0.3m)

V

2

= 1.5 FT (0.5m)

V

T

= V

1

+ V

2

= 1 FT (0.3m)+ 1.5 FT (0.5m)= 2.5 FT (0.8m)

H

1

= 6 FT (1.8m)

H

2

= 2 FT (0.6m)

H

R

= H

1

+ H

2

= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)

H

O

= .03 (one 45° + three 90° elbows - 135°)

= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H

T

= H

R

+ H

O

= 8FT (2.4m) + 5.4FT (1.6m) = 13.4FT (4.1m)

H

T

+ V

T

= 13.4FT (4.1m)+ 2.5FT (0.8m) = 15.9FT (4.8m)

Formula 1:

H

T

< 3V

T

3V

T

= 3FT (0.9m) x 2.5FT(0.8m) = 7.5FT (2.3m)

13.4 FT (4.1m) > 7.5 FT (2.3m)

Since this formula is not met, this vent configuration is unacceptable.

Formula 2:

H

T

+ V

T

< 40 FT (12.2m)

15.9FT (4.8m) < 40FT (12.2m)

Since only formula 2 is met, this vent configuration in unacceptable and a new fireplace location or vent
configuration will need to be established to satisfy both formulas.

Example:
V

1

= 1.5 FT (0.5m)

V

2

= 8 FT (2.4m)

V

T

= V

1

+ V

2

= 1.5 FT (0.5m) + 8 FT (2.4m) = 9.5 FT (2.9m)

H

1

= 1 FT (0.3m)

H

2

= 1 FT (0.3m)

H

3

= 10.75 FT (3.3m)

H

R

= H

1

+ H

2

+ H

3

= 1FT(0.3m) + 1FT(0.3m) + 10.75FT(3.3m) = 12.75FT(3.9m)

H

O

= .03 (three 90° elbows + two 45° elbows - 135°)

= .03 (270 + 90 - 135°) = 6.75 FT (2.1m)
H

T

= H

R

+ H

O

= 12.75 FT (3.9m) + 6.75 FT (2.1m) = 19.5 FT (5.9m)

H

T

+ V

T

= 19.5FT (5.9m) + 9.5FT (2.9m) = 29 FT (8.8m)

Formula 1:

H

T

< 3V

T

3V

T

= 3 x 9.5 = 28.5 FT (8.7m)

19.5 FT (5.9m) < 28.5 (8.7m)

Formula 2:

H

T

+ V

T

< 40 FT (12.2m)

29 FT (8.8m) < 40 FT (12.2m)

Since both formulas are met, this vent configuration is acceptable.