PIPING: THIS HEATER MUST BE INSTALLED BY A QUALIFIED GAS TECHNICIAN
FOLLOWING LOCAL CODES PUBLISHED BY THE AUTHORITY HAVING JURISDICTION.
SIZING OF SUPPLY PIPING MUST BE DETERMINED USING THE LENGTH OF PIPE RUN AS
WELL AS TOTAL BTUH RATING OF THE APPLIANCE(S). APPROPRIATE PIPING TABLES
MUST BE USED TO DETERMINE SIZE OF SUPPLY PIPING DEPENDANT ON THE LENGTH
OF RUN FROM SOURCE.


CONNECTING TO AN EXTERNAL FUEL TANK
(BLAZE 800 D)

Beckett CF800 is fitted with 3/8” SAE male fittings and is set up for a 2 line system to eliminate
priming. Ensure fuel tank has an supply line and a return line and connect the supply line to the
3/8” SAE fitting on the inlet side of the fuel filter and the return line to the return fitting located on
the Beckett Burner pump. For a 1 line system remove bypass plug located on inlet port of Beckett
Pump and just connect fuel line to inlet side of fuel filter.


FUEL (BLAZE 800 G)

THIS HEATER WILL OPERATE ON PROPANE OR NATURAL GAS—NOT BOTH. THE
MANIFOLD PRESSURES ARE LISTED ON THE APPROVAL LABEL. TO DETERMINE WHICH
FUEL TO USE SEE RATING PLATE. DO NOT ATTEMPT TO USE THE HEATER WITHOUT
CONSULTING THE RATING PLATE.

NOTE: THE PROPER MAIN BURNER ORIFICE MUST BE INSTALLED AND RATING PLATE
MUST REFLECT THE FUEL THE HEATER IS BURNING. DO NOT OPERATE THE HEATER
WITHOUT CONSULTING THE RATING PLATE.

HEATER CONVERSION MUST BE DONE BY A QUALIFIED TECHNICIAN AND RATING PLATE
MUST REFLECT ANY CHANGE.

THIS UNIT HEATER IS EQUIPPED FOR NATURAL GAS OR LP GAS. THIS UNIT HEATER IS
EQUIPPED WITH ORIFICES SIZED FOR OPERATION WITH NATURAL OR LP GAS. FOR
CONVERSION TO LP (OR NATURAL) GAS SEE INSTRUCTION PLATE ON THE APPLIANCE.
ORIFICES NECESSARY FOR LP OR NATURAL GAS CONVERSION ARE PROVIDED.

FOR NATURAL GAS WITH BECKETT CG10A BURNER REMOVE PROPANE ORIFICE.
FOR LP GAS WITH BECKETT CG10A BURNER WHEN PROPANE ORIFICE IS INSTALLED.

HOSES