The temperature controller protocols should be checked every heating season to ensure the burner will shutdown if
temperature exceeds 250 F (US)/290 F (CA) at the outlet duct. This can be accomplished by restricting the air flow
through the unit. After tests are complete, remove restrictors as both inlet and outlet ducts must be open for proper
operation.

The temperature controller setting of 120F has been selected to allow for preheating of the heat exchanger to ensure
that only heated air is allowed to enter the space. Upon satisfying the need for heat, the temperature controller will
continue to run the supply fan until the heat exchanger has cooled sufficiently. This feature will help prolong the life of
the heat exchanger. The temperature controller must be replaced if the fan motor does not shut off after the heat
exchanger has cooled down.

Temperature Controller Protocols

Fan Turns on at 120 F

Out # 2 is set at 215ºF (This will cycle the burner off 215ºF and back on at 185ºF.) If the burner reset light goes on; you
need to go into the burner compartment. For the Beckett CF800 oil burner the Beckett Genisys controller located on
the control panel must be pressed.

There is a high limit switch set at 250ºF(This will cause burner to go out on high temp.)

During cool down the unit cools to 80F and then shuts down.


ELECTRICAL
Ensure all conduit (BX) connectors are tight. Open control panel door and burner compartment and check connections
are tight and no frayed wires exposed.

FAN
Check for dust or dirt build up on blades. Run heater to check for fan vibration. Replace fan blade if vibration is
noticeable. The flow of combustion and ventilation air must not be obstructed. Be sure to check the fan assembly and
ensure that the motor and blade are operating properly.

MOTOR
No lubrication is necessary since the bearings are the sealed type. Clean motor of existing dust or dirt.

HEAT EXCHANGER

If a smoky condition continues even after adjusting the air assembly, the heat exchanger should be thoroughly
cleaned.

FUEL FILTER (OIL OPERATION)
Replace cartridge every six months of normal usage.

NOTE: FLOW OF COMBUSTION AND VENTILATION AIR CANNOT BE OBSTRUCTED



FLAME DETECTOR (OIL OPERATION)
When doing maintenance, turn on machine and run. After having machine run for a few minutes, press red button on
primary control. Hold for one second and then release. If light flashes once or twice or three times, cad cell is
functioning properly. If flashes four times, check alignment and proper flame. If correct a cleaning of the face of the
cad cell with a soft non-abrasive cloth is recommended. If light flashes 4 times, follow above steps. If flashing four
times persists, replace cad cell.

LED FLASHES

CAD CELL RESISTANCE

1

0-400 Ohms