2-12. Electrical Service Guide

Input Voltage

200

230

460

575

Input Amperes At Rated Output

50

44

22

17

Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes

80

70

35

25

Min Input Conductor Size In AWG/Kcmil

8

8

10

12

Max Recommended Input Conductor Length

In Feet (Meters)

93 (28)

124 (38)

329 (100)

313 (95)

Min Grounding Conductor Size In AWG/Kcmil

8

8

10

12

Reference: 1996 National Electrical Code (NEC)

S-0092J

2-13. Selecting A Location And Connecting Input Power

Have only qualified persons make
this installation.

1

Rating Label

Supply correct input power.

Y

Special installation may be
required where gasoline or
volatile liquids are present –
see NEC Article 511 or CEC
Section 20.

801 788-A / Ref. 800 797-C

18 in (457 mm)

for airflow

Size and ratings must comply with ap-
plicable codes. Install conductors in
conduit or equivalent into a deener-
gized line disconnect device (see
Section 2-12).