F300 electronic air cleaner, Fig. 20. troubleshooting guide – Honeywell F300 Manuel d'utilisation

Page 21

Advertising
background image

F300 ELECTRONIC AIR CLEANER

21

68-0240EF-5

Fig. 20. Troubleshooting Guide.

NO

TO USE THIS CHART:

START

OFF

ON

YES

YES

REPLACE LIGHT/SWITCH ASSEMBLY.

MAKE SURE ELECTRONIC CELLS ARE CLEAN, DRY AND PROPERLY INSTALLED.

MAKE SURE METAL PREFILTERS ARE POSITIONED ON THE SIDE WHERE

AIR ENTERS THE AIR CLEANER, AND THAT POST-FILTERS (IF ANY) ARE

POSITIONED ON THE SIDE WHERE AIR LEAVES THE AIR CLEANER.

TURN THE POWER SWITCH ON THE AIR CLEANER ON, AND TURN THE

HVAC FAN ON.

CHECK THE SYSTEM LIGHT

ON THE AIR CLEANER.

PUSH TEST BUTTON ON THE

AIR CLEANER DOOR AND

LISTEN FOR SNAPPING SOUND.

NO

TURN OFF AIR CLEANER POWER

SWITCH. REMOVE THE DOOR AND

CHECK THAT THE CONTACTS ON

THE INSIDE OF THE TEST BUTTON

ARE OK.

YES

AIR CLEANER IS

FUNCTIONING PROPERLY.

CELLS OK.

REPLACE AIR

CLEANER

POWER SUPPLY.

INSPECT THE CELLS FOR

— BENT COLLECTOR PLATES

— BROKEN IONIZER WIRES

— DIRT ACCUMULATION ON

THE INSULATORS

— DAMAGED CONTACTS ON

THE TERMINAL BOARD AT

THE END OF THE CELL

NO

SHORT

CHECK FOR CORRECT INPUT

VOLTAGE ACROSS P1 AND P2

TERMINALS ON POWER

SUPPLY BOARD.

REMOVE THE CELLS (LEAVE THE

PREFILTERS IN PLACE). CLOSE THE

ACCESS DOOR AND TURN ON THE

AIR CLEANER POWER SWITCH.

NO

YES

FIX WIRING.

REPLACE AIR CLEANER

POWER SUPPLY.

M13656

FOLLOW THE STEPS IN ORDER; DO NOT SKIP AROUND.
EACH TIME A PROBLEM IS FIXED, GO BACK TO START.
REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS
OUT OK.
NOTE: IF A W8600F AIR CLEANER MONITOR IS CONNECTED
TO THE AIR CLEANER, DISCONNECT THE AIR
CLEANER FROM THE W8600F BEFORE STARTING
THIS PROCEDURE. THE W8600F CAN BE CHECKED
SEPARATELY. SEE W8600F INSTRUCTION SHEET.

1.
2.
3.

THIS STEP EXPOSES

DANGEROUSLY HIGH VOLTAGE.

ONLY A QUALIFIED SERVICE

TECHNICIAN SHOULD ATTEMPT

THIS STEP.

WARNING

WITH AN OHMMETER, CHECK

FOR SHORT BETWEEN:

— CELL FRAME AND IONIZER

WIRES

— CELL FRAME AND COLLECTOR

BLADES

SHORT

DETECTED

REPLACE OR

REPAIR CELLS.

YES

NO

NO

ELECTRONIC AIR CLEANER TROUBLESHOOTING GUIDE

PUSH TEST BUTTON ON THE

AIR CLEANER DOOR AND

LISTEN FOR SNAPPING SOUND.

REPAIR CONTACTS ON TEST BUTTON.

CHECK THE SYSTEM LIGHT

ON THE AIR CLEANER.

REPLACE

CELLS.

OFF

ON

INCORRECT CONVERSION TO MEDIA AIR CLEANER CAN CAUSE FIRE HAZARD.

WHEN CONVERTING AN ELECTRONIC AIR CLEANER TO A MEDIA AIR CLEANER

THE POWER SUPPLY MUST BE REMOVED OR PERMANENTLY DISABLED.

WARNING

THIS AIR CLEANER PRODUCES A TRACE LEVEL OF OZONE AS A BY-PRODUCT OF NORMAL OPERATION, WHICH IS WELL UNDER THE

LIMIT PRESCRIBED BY THE U.S. F.D.A. PLEASE REFER TO YOUR OWNERS MANUAL FOR FURTHER INFORMATION. FOR A REPLACEMENT

OWNERS MANUAL, CALL 1-800-468-1502 OR VISIT http://yourhome.honeywell.com

Advertising