Forza 48 Inch Freestanding Professional Gas Range Installation Instructions Manuel d'utilisation
Page 22

22
GAS REQUIREMENTS
Natural Gas
WC
Supply Pressure
4” (10 mbar)
Min. Line Pressure
5” (12.5 mbar)
Max. Line Pressure
14" (34.9 mbar), .5 psi (3.5 kPa)
GAS REQUIREMENTS
LP Gas
WC
Supply Pressure
11" (27 mbar)
Min. Line Pressure
12" (27.4 mbar)
Max. Line Pressure
14" (34.9 mbar), .5 psi (3.5 kPa)
Pressure Testing
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5 kPa).
This appliance, as well as its individual shut-off valve, must be disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess of 1/2 PSIG (3.5 kPa).
When checking appliance regulator function, make certain pressure of natural gas supply is between 6 and 14 inches of
water column or, if converted for LP gas, between 11 and 14 inches.