Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 245

9469370991 Rev A
239
DGC-2020HD
Table des registres par défaut
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
51-3
Mode
SG2 1P 23600
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-3
Source
SG2 1P 23602
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-3
Enclenchement
SG2 1P 23604
Float
4
L E Ampère
0,9 - 20
51-3
Index de courbe
SG2 1P 23606
Uint32 4
L E s/o
S1 = 0
S2 = 1
L1 = 2
L2 = 3
D = 4
M = 5
I1 = 6
I2 = 7
V1 = 8
V2 = 9
E1 = 10
E2 = 11
A = 12
B = 13
C = 14
G = 15
F = 16
46 = 17
P = 18
51-3
Sens
SG2 1P 23608
Uint32 4
L E s/o
Entrant = 0
Sortant = 1
Non directionnel = 2
51-3
Utilisation de la réinitialisation
instantanée
SG2 1P 23610
Uint32 4
L E s/o
Intégrée = 0
Instantanée = 1
51-3
Constante TD
SG2 1P 23612
Float
4
L E s/o
0 - 9,9
51-3
Constante A
SG2 1P 23614
Float
4
L E s/o
0 - 600
51-3
Constante B
SG2 1P 23616
Float
4
L E s/o
0 - 25
51-3
Constante C
SG2 1P 23618
Float
4
L E s/o
0 - 1
51-3
Constante N
SG2 1P 23620
Float
4
L E s/o
0,5 - 2,5
51-3
Constante R
SG2 1P 23622
Float
4
L E s/o
0 - 30
51-3
Consigne de limitation en
fonction de la tension
SG2 1P 23624
Float
4
L E Volt
30 - 250
51-3
Mode de limitation en fonction
de la tension
SG2 1P 23626
Uint32 4
L E s/o
Désactivé = 0
Contrôle = 1
Limitation = 2
51-3
Configuration d’alarme
SG2 1P 23628
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
51-3
Échelonnage de ligne basse
SG2 1P 23630
Float
4
L E s/o
0,001 - 3
51-3
Source de limitation en fonction
de la tension
SG2 1P 23632
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-3
Constante Q
SG2 1P 23634
Float
4
L E s/o
0,1 - 10
51-3
Mode
SG2 3P 23636
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-3
Source
SG2 3P 23638
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-3
Enclenchement
SG2 3P 23640
Float
4
L E Ampère
0,9 - 20