DGC-2020HD
Table des registres par défaut
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
51-1
Mode
SG2 1P 23024
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-1
Source
SG2 1P 23026
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-1
Enclenchement
SG2 1P 23028
Float
4
L E Ampère
0,9 - 20
51-1
Index de courbe
SG2 1P 23030
Uint32 4
L E s/o
S1 = 0
S2 = 1
L1 = 2
L2 = 3
D = 4
M = 5
I1 = 6
I2 = 7
V1 = 8
V2 = 9
E1 = 10
E2 = 11
A = 12
B = 13
C = 14
G = 15
F = 16
46 = 17
P = 18
51-1
Sens
SG2 1P 23032
Uint32 4
L E s/o
Entrant = 0
Sortant = 1
Non directionnel = 2
51-1
Utilisation de la réinitialisation
instantanée
SG2 1P 23034
Uint32 4
L E s/o
Intégrée = 0
Instantanée = 1
51-1
Constante TD
SG2 1P 23036
Float
4
L E s/o
0 - 9,9
51-1
Constante A
SG2 1P 23038
Float
4
L E s/o
0 - 600
51-1
Constante B
SG2 1P 23040
Float
4
L E s/o
0 - 25
51-1
Constante C
SG2 1P 23042
Float
4
L E s/o
0 - 1
51-1
Constante N
SG2 1P 23044
Float
4
L E s/o
0,5 - 2,5
51-1
Constante R
SG2 1P 23046
Float
4
L E s/o
0 - 30
51-1
Consigne de limitation en
fonction de la tension
SG2 1P 23048
Float
4
L E Volt
30 - 250
51-1
Mode de limitation en fonction
de la tension
SG2 1P 23050
Uint32 4
L E s/o
Désactivé = 0
Contrôle = 1
Limitation = 2
51-1
Configuration d’alarme
SG2 1P 23052
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
51-1
Échelonnage de ligne basse
SG2 1P 23054
Float
4
L E s/o
0,001 - 3
51-1
Source de limitation en fonction
de la tension
SG2 1P 23056
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-1
Constante Q
SG2 1P 23058
Float
4
L E s/o
0,1 - 10
51-1
Mode
SG2 3P 23060
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-1
Source
SG2 3P 23062
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-1
Enclenchement
SG2 3P 23064
Float
4
L E Ampère
0,9 - 20