Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 215

9469370991 Rev A
209
DGC-2020HD
Table des registres par défaut
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
81-3
Mode
SG2
21656
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-3
Source
SG2
21658
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-3
Enclenchement
SG2
21660
Float
4
L E Hertz
37,5 - 66
81-3
Temporisation
SG2
21662
Float
4
L E Milliseconde 0 - 600 000
81-3
Inhibition de tension
SG2
21664
Float
4
L E Pourcentage 1 - 100
81-3
Configuration d’alarme
SG2
21666
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-3
Mode
SG3
21668
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-3
Source
SG3
21670
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-3
Enclenchement
SG3
21672
Float
4
L E Hertz
37,5 - 66
81-3
Temporisation
SG3
21674
Float
4
L E Milliseconde 0 - 600 000
81-3
Inhibition de tension
SG3
21676
Float
4
L E Pourcentage 1 - 100
81-3
Configuration d'alarme
SG3
21678
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-4
Mode
SG0
21680
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-4
Source
SG0
21682
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-4
Enclenchement
SG0
21684
Float
4
L E Hertz
37,5 - 66
81-4
Temporisation
SG0
21686
Float
4
L E Milliseconde 0 - 600 000
81-4
Inhibition de tension
SG0
21688
Float
4
L E Pourcentage 1 - 100
81-4
Configuration d’alarme
SG0
21690
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-4
Mode
SG1
21692
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-4
Source
SG1
21694
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-4
Enclenchement
SG1
21696
Float
4
L E Hertz
37,5 - 66
81-4
Temporisation
SG1
21698
Float
4
L E Milliseconde 0 - 600 000
81-4
Inhibition de tension
SG1
21700
Float
4
L E Pourcentage 1 - 100
81-4
Configuration d’alarme
SG1
21702
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-4
Mode
SG2
21704
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-4
Source
SG2
21706
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-4
Enclenchement
SG2
21708
Float
4
L E Hertz
37,5 - 66
81-4
Temporisation
SG2
21710
Float
4
L E Milliseconde 0 - 600 000
81-4
Inhibition de tension
SG2
21712
Float
4
L E Pourcentage 1 - 100
81-4
Configuration d’alarme
SG2
21714
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-4
Mode
SG3
21716
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-4
Source
SG3
21718
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-4
Enclenchement
SG3
21720
Float
4
L E Hertz
37,5 - 66
81-4
Temporisation
SG3
21722
Float
4
L E Milliseconde 0 - 600 000
81-4
Inhibition de tension
SG3
21724
Float
4
L E Pourcentage 1 - 100
81-4
Configuration d'alarme
SG3
21726
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-5
Mode
SG0
21728
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-5
Source
SG0
21730
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-5
Enclenchement
SG0
21732
Float
4
L E Hertz
37,5 - 66