Ventilation, Operation, Warning – Desa RCLP375 Manuel d'utilisation

Page 8

Advertising
background image

8

100165

VENTILATION

Provide at least a 0,28 m

2

(three-square-foot) opening of fresh, outside air for each

105.500kJ/hr (100,000 BTU/Hr) of rating. This heater requires a fresh-air opening
of at least 1 m

2

(9.75 square feet). Provide extra fresh air if using more heaters.

WARNING ICON

G 001

WARNING

Follow the minimum fresh, outside air ventilation
requirements. If proper fresh, outside air ventilation is not
provided, carbon monoxide poisoning can occur. Provide
proper fresh, outside air ventilation before running heater.

OPERATION

WARNING ICON

G 001

WARNING

Review and understand the warnings in the Safety Information
Section, page 3. They are needed to safely operate this heater.
Follow all local codes when using this heater.

To Start Heater

1. Follow all installation, ventilation, and safety information.
2. Locate heater on stable and level surface. Make sure strong drafts do not blow

into front or rear of heater.

3. Plug power cord of heater into a three-prong, grounded extension cord. Exten-

sion cord must be at least 2 m (6 ft.) long, CSA listed, and of a proper size.

4. Plug extension cord into a 120 volt/60 hertz, three-hole, grounded outlet.
5. Open propane supply valve on propane tank(s) slowly.

Note:

If not opened

slowly, excess-flow check valve on propane tank will stop gas flow. If this
happens, close propane supply valve and open again slowly.

6. Make sure regulator is set between 48 and 138 kPa (7 and 20 psig).

Note:

Higher regulator setting will allow heater to produce more heat.

7. Push start switch to start heater. Heater will start within six seconds.

Note:

If heater does not start, unplug the heater. Wait ten seconds for safety

control to reset, then try again.

To Stop Heater

1. Tightly close propane supply valve on propane tank(s).
2. Wait a few seconds. Heater will burn gas left in supply hoses.
3. Unplug heater.

To Restart Heater

If safety control stops gas flow to heater, motor will continue to run.
To restart heater:
1. Unplug the heater. Wait ten seconds for safety control to reset.
2. Plug in heater. Push start switch.

WARNING ICON

G 001

WARNING

Do not adjust regulator below 48 kPa (7 psig) or above 138
KPa (20 psig). Heater may not run properly.