12 Micro800™ Programmable Controller External AC Power Supply

Publication

2080-IN001A-EN-P - September 2010

Environmental

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…65 °C (-4…149 °F)

Temperature,
surrounding air, max

65 °C (149 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 12... 500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on power ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Voltage variation

IEC 61000-4-11:

30% dips for 1 period at 0° and 180° on AC supply ports

60% dips for 5 and 50 periods on AC supply ports

±10% fluctuations for 15 min on AC supply ports

>95% interruptions for 250 periods on AC supply ports