Mount the module, Module description, Module spacing – Rockwell Automation 2085-OV16_OB16 Micro800 16-Point Sink and 16-Point Source 12/24V DC Output Modules Manuel d'utilisation
Page 6

6 Micro800 16-Point Sink and 16-Point Source 12/24V DC Output Modules
Publication 2085-IN003B-EN-P - September 2012
Mount the Module
For more information on proper grounding guidelines, see the Industrial Automation Wiring
and Grounding Guidelines, publicat
.
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Mounting Dimensions and DIN Rail Mounting
Module Description
Description
Description
1
Mounting screw hole / mounting foot
4
Module interconnect latch
2
Removable Terminal Block (RTB)
5
DIN rail mounting latch
3
RTB hold down screws
6
I/O status LED
This equipment is sensitive to electrostatic discharge (ESD).
Follow ESD prevention guidelines when handling this equipment.
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source
compliant with the following:
Class 2 or Limited Voltage/Current.
45305
Mounting dimensions do not include mounting feet or DIN rail latches.
87 mm (3.15 in.)
90 mm
(3.54 in.)
150 mm (5.91 in.)
44.5 mm (1.75 in.)
2085-OV16 or 2085-OB16
Micro850 Controller
Bus terminator