10 Micro800 16-Point Sink and 16-Point Source 12/24V DC Output Modules
Publication 2085-IN003B-EN-P - September 2012
Isolation voltage
50V (continuous), Reinforced Insulation Type, channel to system
Type tested at 720V AC for 60 s
Enclosure type rating
None (open-style)
North American temp code
T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication
(2)
RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Output Specifications
Attribute
2085-OV16
2085-OB16
Operating voltage range
10…30V DC
On-state voltage, min
10V DC
On-state voltage, nom
24V DC
On-state voltage, max
30V DC
On-state current, max
0.5 A @ 30V DC, per output
8 A, per module
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature, surrounding air, max
65 °C (149 °F)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g – for DIN rail mount
35 g – for panel mount
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
General Specifications
Attribute
2085-OV16
2085-OB16