Installation, Oven location and ventilation – Blodgett CNV14G Manuel d'utilisation

Page 9

Advertising
background image

Installation

5

Oven Location and Ventilation

OVEN LOCATION
The well planned and proper placement of your

oven will result in long term operator convenience

and satisfactory performance.
Certain minimum clearances must be maintained

between the oven and any combustible or nonĆ

combustible construction. See the table below.
In addition, the following clearances are recomĆ

mended for servicing.

D

Oven body sides - 12" (30cm)

D

Oven body back - 12" (30cm)

NOTE: On gas models, routine servicing can usuĆ

ally be accomplished within the limited

movement provided by the gas hose reĆ

straint. If the oven needs to be moved furĆ

ther from the wall, the gas must first be

turned off and disconnected from the oven

before removing the restraint. Reconnect

the restraint after the oven has been reĆ

turned to its normal position.

Left Side Heat Shield
Heat sources should not be near the air vents loĆ

cated on the left hand side of the gas appliance.

Consult the factory for optional protective side

heat shield.
CNV14P/N R9527

Oven

M d l

MINIMUM REQUIRED

CLEARANCES

Model

Right

Side

Left

Side

Back

CNV14E

1"

(25.4mm)

4"

(101.6mm)

6"

(152.4mm)

CNV14G

1"

(25.4mm)

6"

(152.4mm)

6"

(152.4mm)

VENTILATION
The necessity for a properly designed and inĆ

stalled ventilation system cannot be over emphaĆ

sized. The ventilation system will allow the unit to

function properly while removing unwanted vapors

and products of combustion from the operating

area.
The appliance must be vented with a properly deĆ

signed mechanically driven exhaust hood. The

hood should be sized to completely cover the

equipment plus an overhang of at least 6" (15 cm)

on all sides not adjacent to a wall. The capacity of

the hood should be sized appropriately and proviĆ

sions made for adequate makeup air.

WARNING!!
Failure to properly vent the oven can be

hazardous to the health of the operator;

and will result in operational problems,

unsatisfactory baking, and possible damĆ

age to the equipment. Damage sustained

as a direct result of improper ventilation

will not be covered by the Manufacturer's

warranty.

U.S. and Canadian Installations
Refer to your local ventilation codes. In the abĆ

sence of local codes, refer to the National ventilaĆ

tion code titled, Standard for the Installation of

Equipment for the Removal of Smoke and Grease

Laden Vapors from Commercial Cooking EquipĆ

ment", NFPAĆ96Ć Latest Edition.
General Export Installations
Installation must conform with Local and National

installation standards. Local installation codes

and/or requirements may vary. If you have any

questions regarding the proper installation and/or

operation of your unit, please contact your local

distributor. If you do not have a local distributor,

please call Blodgett Combi at 0011Ć802Ć860Ć3700.