6 | SAMLEX AMERICA INC.

SAMLEX AMERICA INC. | 7

SeCtIOn 3 |

Installation

!

WARninG!

Danger of explosion from sparking! Danger of electric shock!
- the solar charge controller may only be connected to the local loads and the

battery by trained personnel and in accordance with the applicable regulations.

- Follow the installation and operating instructions for all components of the

PV system.

- ensure that no cables are damaged.

MoUntinG tHe SoLAR cHARGe contRoLLeR

Mounting location requirements

- Do not mount the solar charge controller outdoors or in wet rooms.
- Do not subject the solar charge controller to direct sunshine or other sources of heat.
- Protect the solar charge controller from dirt and moisture.
- Mount upright on the wall (concrete) on a non-flammable substrate.
- Maintain a minimum clearance of 10 cm below and around the device to ensure

unhindered air circulation.

- Mount the solar charge controller as close as possible to the batteries (with a safety

clearance of at least 30 cm).

Fastening the solar charge controller

- Mark the position of the solar charge controller fastening holes on the wall.
- Drill 4 x 6 mm holes and insert dowels.
- fasten the solar charge controller to the wall with the cable openings facing

down- wards, using 4 oval head screws M4 x 40 (DIN 7996).

connection

Preparing the wiring

The cross section of the connection cable depends on the power output of the solar
charge controller.

contRoLLeR

tyPe

LoAD/MoDULe

cURRent

cRoSS-Section

AWG

inSULAtion

20A

20A

10 mm

2

8

85°C

The table above applies to the following cable lengths:
- 10 m solar module connection cable
- 2 m battery connection cable
- 5 m load connection cable

Consult a dealer if the specified cable lengths are inadequate.