Ul installation requirements sti dome series – STI 1212 Manuel d'utilisation

Page 2

Advertising
background image

04/2010

• The enclosure is rated to protect signaling appliances indoors and in areas of indirect weather exposure. The

cover may be used outdoors only with devices also suitable for outdoor use.

• When covering fire-signaling appliances with this enclosure, some light and sound loss occurs. Please follow

the guidelines listed during installation.

• Strobe light loss values for respective manufacturers are shown below. To determine the new composite candela value

for use with this guard refer to the sample calculation shown below for a manufacturer’s strobe.

• Example: Record the manufacturer's candela value as "A" and the light loss value as "B" and the assembly value

as "C". For example “Sample Company” has a 60 candela strobe with a 30% light transmission loss value. Value

"A" is now 60. Value "B" is (60 times 30% or 0.30) in this case 18. Now value "C" equals value "A" minus value

"B" or 60-18 = 42 candela light source. Now refer to NFPA tables for proper room size that the newly established

value "C" will work in. Submittal installation drawings must show the composite candela value as 42.

• On a dual value strobe such as 15/75 a calculation must be done for each value and the drawing notation

composite value for each number on the strobe.

Performance Review - LIGHT DERATING FACTOR

ADT SECURITY

ADTG1-V SERIES

20%

32%

HONEYWELL

XLS202 SERIES

33%

34%+

AMSECO

SL24W-153075

22%

37%+

HONEYWELL

XLSG1-HV SERIES

20%

32%+

AMSECO – COLORED LENSES

SL24W-153075 A, B, G, OR R

22%

37%+

HONEYWELL

XLSG1-HOV SERIES

20%

37%+

AMSECO – COLORED LENSES

SL24C-3075110 A, B, G, OR R

22%

37%+

MIRCOM

FS-240

22%

37%+

AMSECO – COLORED LENSES

CSL24W-A, B, G, OR R

22%

37%+

MIRCOM

MS SERIES

33%

34%+

AMSECO – COLORED LENSES

CSL24C-A, B, G, OR R

22%

37%+

MIRCOM

MG1-V SERIES

20%

32%+

DETECTION SYSTEMS

GES24 SERIES

27%

37%+

MIRCOM

MG1-HV SERIES

20%

32%+

DETECTION SYSTEMS

GES24-15/75

27%

37%+

MIRCOM

MG1-HOV SERIES

20%

32%+

EST / EDWARDS

2440S SERIES

33%

34%+

MIRTONE

MG1-V SERIES

20%

32%

EST / EDWARDS

202 SERIES

33%

34%+

NATIONAL TIME & SIGNAL

GES24 SERIES

27%

37%

EST / EDWARDS

G1-V SERIES

20%

32%+

NATIONAL TIME & SIGNAL

GES24-15/75

27%

37%+

EST / EDWARDS

G1-HV SERIES

20%

32%+

POTTER ELECTRIC

AS-24-153075R

22%

37%+

EST / EDWARDS

G1-HOV SERIES

20%

32%+

POTTER ELECTRIC

AS-24-153075W

22%

37%+

EST / EDWARDS

EG1-V SERIES

20%

32%+

SECUTRON

GES24 SERIES

27%

37%+

EST / EDWARDS

EG1-HV SERIES

20%

32%+

SECUTRON

GES24-15/75

27%

37%+

EST / EDWARDS

EG1-HOV SERIES

20%

32%+

SIEMENS

202 SERIES

33%

34%+

FARADAY LLC

2700

23%

33%+

SIEMENS

G1-V SERIES

20%

32%+

GENTEX

GES24 SERIES

27%

37% +

SIEMENS

U-MCS SERIES

23%

33%+

GENTEX

GES24-15/75

27%

37% +

SYSTEM SENSOR

SS24110ADA

26%

36%+

HARRINGTON SIGNAL

GES24 SERIES

27%

37% +

SYSTEM SENSOR

P2, PC2, P4, PC4, SX, SC

39%

28%

HARRINGTON SIGNAL

GES24-15/75

27%

37% +

WHEELOCK

RSS-24MCW

34%

31%

HONEYWELL

XLSG1-V SERIES

20%

32%+

WHEELOCK

RSS-24MCC

36%

35%

ZITON PTY LTD

ZG1-V SERIES

20%

32%+

MANUFACTURER

SERIES

STI-1215/1217/1219 STI-1225/1227/1229

MANUFACTURER

SERIES

STI-1215/1217/1219 STI-1225/1227/1229

SOUND DERATING FACTOR for STI-1215, STI-1217, STI-1219

HORNS: Amseco Audible Horn Sounders: 6.2 dBA; System Sensor: 3.1 dBA

SPEAKERS: Siemens Adapter Series (0.5, 1, or 2 watt taps only): 4.1 dBA

SAFETY TECHNOLOGY INTERNATIONAL, INC. • 2306 AIRPORT ROAD • WATERFORD • MICHIGAN 48327-1209 • PHONE: 248-673-9898 • FAX: 248-673-1246 • INFO @ www.sti-usa.com

UL INSTALLATION REQUIREMENTS

STI DOME SERIES

CAUTION

+ Indicates notification appliance can also be used with STI Heater Domes models STI-1229HTR or STI-1229HTR240.

• Ce boîtier est homologué pour protéger les appareils de signalisation d’incendie à l’intérieur et dans les zones d’exposition

indirecte aux intempéries. Le couvercle ne peut être utilisé à l’extérieur qu’avec les appareils appropriés pour une utilisation à
l’extérieur aussi.

• Le fait de couvrir les appareils de signalisation d’incendie au moyen de ce boîtier risque d’entraîner une certaine perte lumineuse

et sonore. Veuillez vous conformer à ces directives lors de l’installation.

• Les valeurs de perte de lumière stroboscopique publiées par les fabricants respectifs sont présentées ci-dessous. Pour

déterminer la nouvelle valeur candéla composite pour une utilisation avec cette protection, reportez-vous au modèle de calcul
montré pour le stroboscope d’un fabricant donné.

• Exemple: Inscrivez la valeur candéla « A » du fabricant et la valeur de perte de lumière « B » et la valeur de l’ensemble « C ».

Par exemple, la « Société modèle » possède un stroboscope de 60 candélas avec une valeur de perte de diffusion lumineuse
de 30 %. La valeur « A » sera alors de 60. Et la valeur « B » sera dans ce cas de 18 (60 fois 30 % ou 0,30). À présent, la valeur
« C » est égale à la valeur « A » moins la valeur « B », ou 60 - 18 = 42 candélas. Reportez-vous maintenant aux tableaux de la
NFPA pour la taille correcte de la pièce compatible avec la valeur « C » nouvellement créée. "C" travailler. Les schémas
d’installation à soumettre doivent afficher la valeur de candéla composite comme étant 42.

• Dans le cas d’un stroboscope double-valeur, telle que 15/75, un calcul doit être effectué pour chaque valeur et pour la valeur

composite du schéma des cotes relatif à chaque valeur sur le stroboscope.

Attention