STI 1212 Manuel d'utilisation

Installation of sti-1217 stopper, Dome for horn/speaker/strobe

Advertising
background image

Safety Technology International, Inc.

2306 Airport Road • Waterford, Michigan 48327-1209
Phone: 248-673-9898 • Fax: 248-673-1246
Toll Free: 800-888-4784 • E-mail: [email protected]
Web: www.sti-usa.com

Safety Technology International (Europe) Ltd.

Unit 49G Pipers Road • Park Farm Industrial Estate • Redditch
Worcestershire • B98 0HU • England • Tel: 44 (0) 1527 520 999
Fax: 44 (0) 1527 501 999 • Freephone: 0800 085 1678 (UK only)
E-mail: [email protected] • Web: www.sti-europe.com

INSTALLATION OF STI-1217 STOPPER

®

DOME FOR HORN/SPEAKER/STROBE

All specifications and information shown were current as of publication and are subject to change without notice.

INSTALLATION NOTES

1. To minimize strobe light loss, regardless of the type of horn/strobe appliance used, the clear

section (not the section containing the cutout slots) must be centered over the strobe light
lens. Failure to follow these instructions may lead to light loss transmission.

2. Stopper Dome must be installed to comply with applicable NEC, NFPA and local codes.
3. Stopper Dome may be installed outdoors when appliance carries an outdoor rating.
4. If added protection is needed due to environmental conditions, order SUB-123 Enviro kit.

Electronic warranty form at www.sti-usa.com/wc14

1217IS APRIL2006

CLEANING INSTRUCTIONS

Rinse with water to remove abrasive dust and dirt. Wash with soap
or mild detergent, using a soft cloth (do not scrub). Rinse once
more then dry with a soft cloth or chamois. To remove grease or
wet paint, rub gently with a cloth wetted with naphtha. Then wash
and rinse. DO NOT USE RAZOR BLADES.

INSTALLATION INSTRUCTIONS - REFER TO EXPLODED VIEW

1. Using enclosure assembly as a template, place against

mounting surface at proper location according to NFPA 72.

2. Mark and drill (4) holes 1/4 in. (6.3mm) diameter, 1 in.

(25mm) deep.

3. Insert the (4) anchors into the wall.
4. Mount frame assembly to wall with screws.
5. Install electrical fittings as needed.
6. Install horn/strobe appliance (except for retrofit applications).
7. Install cover with clips and screws.
8. Test appliance according to appliance manufacturer’s

instructions.

2.87 in.(73mm)

7.87 in.(200mm)

1.62 in.(41mm)

7.37 in.(187mm)

STI-1215

COVER

STI-1212

SPACER

PLASTIC INSERT
(1) PROVIDED

CONDUIT SEALING GASKET

SUB-123 ENVIRO KIT

ADHESIVE BACKED GASKET

SPACER TO MOUNTING SURFACE

EXISTING

WARNING

APPLIANCE

19033 ANCHOR

(4) PROVIDED

01212 SPACER

19013 SCREW

#10 x 1-1/2 in.

(4) PROVIDED

GASKET

(COVER TO SPACER)

01215 HORN/STROBE

PROTECTIVE COVER

19049 WASHER (6) PROVIDED

19047 #8 - 32 x 3/8 in.

SOCKET HEAD CAP SCREW

(6) PROVIDED

IF ADDED PROTECTION IS NEEDED
DUE TO ENVIROMENTAL CONDITIONS
ORDER SUB-123 ENVIRO KIT
ALSO INCLUDES (6)
#8-32 X 3/4 in. SOCKET CAP SCREWS

PLASTIC INSERT
(1) PROVIDED

CONDUIT SEALING GASKET

SUB-123 ENVIRO KIT

ADHESIVE BACKED GASKET

SPACER TO MOUNTING SURFACE

EXISTING

WARNING

APPLIANCE

01212 SPACER

19013 SCREW

#10 x 1-1/2 in.

(4) PROVIDED

GASKET

(COVER TO SPACER)

01225 STROBE

PROTECTIVE COVER

19049 WASHER (6) PROVIDED

19047 #8 - 32 x 3/8 in.

SOCKET HEAD CAP SCREW

(6) PROVIDED

19033 ANCHOR

(4) PROVIDED

IF ADDED PROTECTION IS NEEDED
DUE TO ENVIROMENTAL CONDITIONS
ORDER SUB-123 ENVIRO KIT
ALSO INCLUDES (6)
#8-32 X 3/4 in. SOCKET CAP SCREWS

2.87 in.(73mm)

7.87 in.(200mm)

1.62 in.(41mm)

7.37 in.(187mm)

STI-1215

COVER

STI-1212

SPACER

REMARQUES SUR L’INSTALLATION

1. Afin de minimiser la perte de lumière stroboscopique, quel que soit le type d’alarme sonore/de

stroboscope utilisé, la section dégagée (et NON la section contenant les fentes de découpe), doit
être centrée sur l’objectif stroboscopique. Le fait d’omettre ces instructions risque d’entraîner la
perte de diffusion de la lumière.

2. Le dôme Stopper doit être installé de sorte à être conforme avec les normes NEC, NFPA applicables

et les codes locaux.

3. Il est possible d’installer un dôme Stopper à l’extérieur lorsque l’appareil est homologué pour

utilisation à l’extérieur.

4. S’il est nécessaire d’ajouter une autre protection en raison des conditions environnementales,

commandez la trousse Enviro, SUB-123.

PRODUCT DIMENSIONS

Advertising
Ce manuel est liée aux produits suivants: