Thermostat Specifications
Operating Voltage
18-30V AC
Maximum Load Current
1 Amp Max per Output Terminal
4 Amp Total Load
Output Type
Latching Relays
Batteries
2 AA Alkaline in Series
Battery Life
2 Years Typical
Ambient Operating Temperature
14 °F (-10 °C) to 122 °F (50 °C)
Storage Temperature
-4 °F (-20 °C) to 140 °F (60 °C)
Operational Mode Chart:
Demand
Conventional
(Non-HP)
Heat Pump
(HP) Elec
Heat Pump
(HP) Gas
First Stage Heat
W1 + G*
Y1 + G + B
Y1 + G + B
Second Stage Heat W1 + W2 + G*
Y1 + Y2 + G + B
or
Y1 + W2 + G + B
Y1 + Y2 + G + B
or
Y1 + W2 + G + B
Third Stage Heat
N/A
Y1 + Y2 + E +
G + B
or
Y1 + W2 + E +
G + B
E + B
Emergency Heat
N/A
Y1 + G + O
Y1 + G + O
First Stage Cool
Y1 + G
Y1 + Y2 + G + O Y1 + Y2 + G + O
Second Stage Cool
Y1 + Y2 + G
E + G
E