5

Venting Requirements

■ Vent system (if needed) for installation is not included.
■ Vent system must terminate to the outside.
■ Do not terminate the vent system in an attic or other

enclosed area.

■ Do not use 4" (10.2 cm) laundry-type wall caps.
■ Use metal vent only. Rigid metal vent is recommended. Do

not use plastic or metal foil vent.

For the most efficient and quiet operation:
■ The length of the vent system and number of elbows should

be kept to a minimum to provide efficient performance. The
size of the vent system should be uniform.

■ Do not install two elbows together.
■ Vent system can terminate either through the roof or wall.
■ For the most efficient and quiet operation, it is recommended

that the range be vented vertically through the roof through
7" (17.8 cm) round vent system.

■ Use duct tape to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around

the cap.

Venting Methods

Determine which outside venting method needs to be used. It is
recommended that the vent system be installed before installing
the hood.

NOTE: If a non-vented (recirculating) installation is desired, follow
instructions in the “Make Electrical Connection” section.

Roof venting

Wall venting

7" (17.8 cm) round
or 3-1/4" x 10"
(8.3 x 25.4 cm)
through roof

roof cap

24" (61 cm) to
30" (76.2 cm)
above cooking
surface

Round vent:
Use 7" (17.8 cm)
round damper
(purchased
separately)

wall
cap

3-1/4" x 10"
(8.3 x 25.4 cm)
through the wall

7" (17.8 cm)
round
or 3-1/4" x 10"
(8.3 x 25.4 cm)
through the wall

24" (61 cm) to
30" (76.2 cm)
above cooking
surface

90° elbow

wall cap

1 — 90° elbow

=

5 ft. (1.5 m)

1 — wall cap

=

0 ft.

(0 m)

8 ft. (2.4 m) straight

=

8 ft. (2.4 m)

system length

=

13 ft. (3.9 m)

6 ft. (1.8 m)

2 ft.

(0.6 m)

Example vent

system

Vent piece 7" (17.8 cm) round

45° elbow

2.5 feet

(0.8 m)

90° elbow

5.0 feet

(1.5 m)

7" (17.8 cm)

0 feet

wall cap

(0 m)

Calculating Vent System Length

To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.

Use 3

¹⁄₄" x 10" (8.3 x 25.4 cm) or 7" (17.8 cm) round vent with a

maximum length of 65 feet (19.8 m) for vent system. For best
performance, use no more than three 90° elbows. To calculate the
length of system you need, add the equivalent feet for each vent
piece used in the system. See the examples below.

3-1/4" x 10" (8.3 x 25.4 cm) vent system

7" (17.8 cm) vent system

Recommended standard fittings

Recommended standard fittings

Vent piece

7" (17.8 cm) round

3

¹⁄₄" x 10"

4.5 feet

(8.3 x 25.4 cm) (1.4 m)
to 7" (17.8 cm)

3

¹⁄₄" x 10"

5 feet

(8.3 x 25.4 cm) (1.5 m)
to 7" (17.8 cm)
90° elbow

3-1/4" x 10"
(8.3 x 25.4 cm)
elbow

wall cap

1 — 90° elbow

=

5 ft. (1.5 m)

8 ft. (2.4 m) straight

=

8 ft. (2.4 m)

1 — wall cap

=

0 ft.

(0 m)

system length

=

13 ft. (3.9 m)