Bradford White RE2H50R10 Manuel d'utilisation

Heat pump, Hybrid, Electric/standard

Advertising
background image

Temperature Sensors

Sensor

Description

Normal tem-

perature Range

Resistance

range in ohms

Resistance at

77º F

T2

Tank

30º F-160º F

34K-1.75K

10K

T3a

Evaporator

Inlet

15º F-130º F

57K-3K

10K

T3b

Evaporator

Outlet

15º F-130º F

57K-3K

10K

T4

Compressor

Outlet

30º F-250º F

188K-3K

55K

T5

Ambient

15º F-130º F

57K-3K

10K

Bradford White Heat Pump Water Heater RE2H50R10-1NCWW

IMPORTANT SAFETY NOTICE

For your family’s comfort, safety and convenience, it

is recommended this water heater be installed and

serviced by a plumbing professional. Any attempt to

repair a major appliance may result in personal injury and

property damage. The manufacturer or seller cannot be

responsible for the interpretation of this information, nor

can it assume any liability in connection with its use. This

quick reference guide is provided for information purposes

only and does not replace, modify or change in any

manner the Owner’s Manual and Installation Instructions.

DISCONNECT POWER BEFORE SERVICING
IMPORTANT- RECONNECT ALL GROUNDING DEVICES

All parts of this appliance capable of conducting electrical

current are grounded. If grounding wires, screws, straps,

clips, nuts or washers used to complete a path to ground

are removed for service, they must be returned to their

original condition and properly fastened.

SPECIFICATIONS

Capacity .......................................................................50 US gal

Tank Max Working Pressure .................................. 150 PSI

Water Temperature Set Point Range .....100F - 140F

Electrical ...................................... 240/208VAC 60 Hz 1-PH

Circuit Breaker ..............................................................30 Amp

Upper Element Wattage ...................................4500/3380

Lower Element Wattage ...................................4500/3380

REFRIGERATION SYSTEM

Compressor ...................................................................... 600 W

Refrigerant Charge (R134a) .................................. 27.34 oz

Compressor LRA ............................................................ 21.0A

Compressor LRA with Capacitor ............................19.6A

Compressor RLA ...............................................................3.0A

Compressor RLA with Capacitor ...............................4.5A

High Pressure (at 70 ambient) ............................ 331 PSIA

Low Pressure (at 70 ambient) ............................. 107 PSIA

SERVICE MODE

The Service Mode can be accessed by pressing and holding the

UP Arrow and Enter buttons simultaneously for 5 seconds. You

will first hear a single beep when pressing the buttons, then a

two-tone sound indicating the action was successful. A moment

later, you will see the first display of the thermistor T2 alternating

with its temperature displayed in the units selected (degrees F

or C). The Service Mode will time out after 15 minutes of button

inactivity.
Three functions are available in Service Mode: View Thermistors,

Heating Component Status and Control, and View Faults and

Counters. You may switch from one function to another by

pressing the Mode button. Service Mode starts with the View

Thermistors function with the Heat Pump (Only) Mode LED (top) lit.

Pressing the Mode button will switch to the Heating Components

Status and Control function with the Hybrid LED (2nd from top) lit.

Pressing the Mode button again will switch to the View faults and

Counters function will be 3rd LED from the top lit. Pressing the

Mode button again will return to the top LED and the Thermistors

function.

An explanation of the three functions follows:
View Thermistor - Each of the 5 thermistors can be monitored for

the temperature they sense. The thermistor designation appears

on the display and alternates with the temperature in degrees

of the units selected - Fahrenheit or Celsius. Pressing the Down

Arrow button switches the display to the next thermistor in the list.

The following table shows the thermistors’ designations and their

function in the unit.

Designation

Function

T2

Tank (Water) Temperature

T3a

Evaporator Inlet Temperature

T3b

Evaporator Outlet Temperature

T4

Compressor Discharge Temperature

T5

Ambient Air Temperature

Heating Component Status and Control - This function displays

the status (on/off) for each of the heating components - Lower

Element, Upper Element and Compressor - and allows you to turn

it on or off. The first component is the Lower electric element (LE).

On status is signified by a 1 and off is 0. Pressing the Down Arrow

button switches to the Upper Element (UE). Pressing Down Arrow

once more switches to the Compressor (Co). only one component

can be on at one time. The electric elements will only stay on for

5 minutes without refreshing by pressing any button on the front

panel. The compressor timeout is 10 minutes.
View Faults and Counters - The control counts the number of

times a fault is recorded. A fault is not displayed until 10 counts

have been recorded (or 5 counts for Dirty Filter) to ensure a true

failure has occurred. For example, if the upper element were to

fail, each time the control energized the upper element, but the

element failed to draw current, the count would increase by 1.

If however, the element responded normally, the count would

decrease by 1 down to 0, but not less than zero. This function

starts by displaying any fault codes (counters that have reached

10) in the system. Pressing Down Arrow takes you to the next

fault code, if any. If no fault codes are active, “- - -” is displayed.

Pressing the Filter button switches the display to the fault counters.

The fault counter designation alternates in the display with its

count value. For example, if the thermistor T3a has registered

3 more failures than passes, its value will be 3 and the display

will alternate between “F5” and “3”. The fault codes and their

explanations are listed in the fault code table shown on page 2.

To clear all fault codes and fault counters, press and hold the Enter

button for 5 seconds and listen for the Hold Tones.
Exiting Service Mode - To exit Service Mode without waiting for

15 minute timeout, press and hold the Up Arrow and Down Arrow

simultaneously for 5 seconds and listen for two beeps.

Heat Pump

(Only)

Utilizes heat pump only.

Hybrid

Utilizes the heat pump and

electric heating elements.

Electric/Standard

(Fan Off)

Utilizes electric elements

only. Stops the fan, the

heat pump and the flow of

cool air.

Vacation

Use this mode for periods

away from home.

Mode

Press this button to toggle

through the various heating

modes. Press and hold to

switch between ºF and ºC.

Display

Displays the current

temperature or the number

of days for vacation mode.

Arrow Pad

Use the up and down

arrows to manually change

the water temperature, or to

select days for Vacation Mode.

Enter

Press to confirm selections.

Filter

The red LED indicates that

the filter needs cleaning.

Press and hold to reset.

T2 Tank Sensor

T3b Evaporator

Outlet Sensor

T4 Compressor

Outlet Sensor

T3a Evaporator

Inlet Sensor

T5 Ambient Air

Sensor

238-50804-00A 31-75034 03-14

PASS/FAIL COMPONENT OPERATION

Selected Mode

SS

LE

UE

Temporary Mode (if component failure is detected)

Any

P

P

P

Runs in selected mode

Any

F

P

P

Electric mode

Hybrid

P

F

P

Hybrid Mode (but uses SS when LE is called for)

Electric

P

F

P

Electric Mode (UE only)

Heat Pump (Only)

P

F

P

Heat Pump (Only) mode

High Demand/Boost

P

F

P

High Demand/Boost (but uses SS when LE is called for)

Hybrid

P

P

F

Control uses SS and LE based on demand algorithm

Electric

P

P

F

LE Only Mode

Heat Pump (Only)

P

P

F

Heat Pump (Only) Mode

High Demand/Boost

P

P

F

High Demand/Boost (but uses LE when UE called for)

Any

F

F

P

Electic Mode (UE only)

Any

P

F

F

Heat Pump (Only) Mode

Any

F

P

F

LE Only Mode

Any

F

F

F

Electric Mode, displays 3 fault codes

SS = Sealed System

LE = Lower Element

UE= Upper Element

Double wall heat exchanger, suitable for potable water

connection.

CAUTION

Advertising
Table des MATIÈRES