ELECTRICAL

WARNING

Disconnect the power supply before installation of the heater. Lock the switch in

the “OFF” (open) position and/or tag the switch to prevent unexpected power application.

For heaters marked "IIC", insure to loosen the setscrew before removing the cover. Installation and

wiring of the heater must adhere to all applicable codes.

GENERAL

1. Use only copper conductors and approved explosion-proof wiring methods during installation. Refer to the

“Technical Data” Table or heater data plate for the voltage, amperage and wattage ratings when sizing

for the appropriate conductors. All supply conductors should be rated for operating at temperatures up to

194°F (90°C).

2. Supply voltage must be within 10% of the data plate rating. External over-current protection is required and

must meet data plate ratings for voltage, amperage and frequency.

FIELD WIRING

1. Heater has been supplied with an enclosure that has a standard 3/4” NPT threaded opening to

accommodate the line conductors (see Figure 4 for connection details). Use wire connectors rated for

minimum 194°F (90°C).

NOTE: If remote thermostats other than the factory supplied are used, ensure that they will not allow

the room temperature to exceed ambient temperature limitations of the heater (104°F/40°C) and

are suitable for the area’s hazardous atmosphere classification. When using any control devices,

ensure that the voltage and amperage ratings match the heater’s electrical ratings. If not, a

contactor may be required.

FINAL INSPECTION

1. Before application of electrical power:

a. check that all connections are secured and comply with the wiring diagram (see Figure 4) and

applicable code requirements,

b. confirm that the supply voltage is compatible with the data plate specifications,

c. remove any foreign objects from the heater, and

d. ensure all external fittings and enclosure covers are secured.

Element

Room

Thermostat

FIGURE 4: Wiring Diagram for remote mount and built-in room thermostats

L1*
L2

Element

* On 120V units

L1 represents

neutral

– 5 –

FIGURE 3: Installation Clearances