CCI Thermal Technologies CX1 - ProVector Explosion-Proof Convection Heater Manuel d'utilisation

Cx1 provector, Series, Owner’s manual

Advertising
background image

OWNER’S MANUAL

CX1 ProVector

®

Series

Electric Convection Air Heaters for Hazardous Locations

APPROVED LOCATIONS

Electric convection air heaters are cULus listed for

the following hazardous locations:

(without built-in thermostat)

Class I, Div. 1 & 2, Groups A, B, C & D

Class I, Zones 1 & 2, Groups IIA, IIB, IIC

Temperature Code T2A 536°F (280°C),

T3 392°F (200°C)

(with built-in thermostat)

Class I, Div. 1 & 2, Groups A, B, C & D

Class I, Zones 1 & 2, Groups IIA & IIB, IIC

Temperature Code T2A 536°F (280°C), T3 392°F (200°C)

For details of hazardous locations with potential for

explosion, refer to the Canadian Electrical Code,

Part 1, Section 18 or National Electrical Code

Articles 500 - 516.

Ruffneck

TM

and ProVector

®

are registered trademarks of CCI Thermal Technologies Inc.

Copyright © 2013. All rights reserved.

Pt. No. 6348.Rev.16.01

Printed in Canada

Issue Date: February 2013

– 1 –

This manual covers installation, maintenance, repair and parts.

WARNING!

READ ALL IMPORTANT NOTICES ON PAGE 3.

PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL.

Failure to do so may be dangerous and may void certain provisions of your warranty.

CX1 - 120 1 60 - 012 - T2A - IIB - T

MODEL CODING

KILOWATTS

0075 - 0.75kW 018 - 1.8kW

036 - 3.6kW

0083 - 0.83kW 0226 - 2.26kW 0476 - 4.76kW

009 - 0.90kW 025 - 2.5kW

048 - 4.8kW

0113 - 1.13kW 0269 - 2.69kW 0528 - 5.28kW

012 - 1.2kW

0301 - 3.01kW 0568 - 5.68kW

0125 - 1.25kW 0333 - 3.33kW 076 - 7.6kW

0135 - 1.35kW 0359 - 3.59kW

MODEL SERIES

VOLTAGE

120V

208V

240V

277V

380V

400V

415V

480V

600V

PHASE

UNITS IN

SINGLE PHASE

ONLY

FREQUENCY

50 or 60 HERTZ

T-CODE

T2A - 536ºF (280ºC)

T3 - 392ºF (200ºC)

HAZARDOUS

LOCATION

IIB

IIC

BUILT-IN T'STAT

ADD 'T' FOR

T'STAT