Series ok3 – infrared radiant heaters – CCI Thermal Technologies GX - Heavy Duty Forced Air Unit Heater Manuel d'utilisation

Page 3

Advertising
background image

MI182 REV.8 Page 1 of 2

CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3 – INFRARED RADIANT HEATERS

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that

combustible materials are always kept at a safe distance from the radiant energy. This heater is

not intended for use in hazardous areas where flammable vapours, gases or liquids or other

combustibles are present. Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations. Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum space clearances from combustibles, when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the safety of this equipment and

adequate back-up controls and safety

devices must be installed. Failure to

comply could result in personal injury

and/or property damage.

Heaters must be wired by qualified

personnel in compliance with local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture

accumulation can cause fault to the

element sheath generating arcing and

releasing molten metal. Install proper

ground fault protection to prevent

personal injury and/or property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1". The standard Type 1 enclosure

is suitable for dry, indoor locations only in non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

cm

[12”

]

FIG. 1 – MOUNTING CLEARANCES

MI182 REV.8 Page 1 of 2

CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3 – INFRARED RADIANT HEATERS

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that

combustible materials are always kept at a safe distance from the radiant energy. This heater is

not intended for use in hazardous areas where flammable vapours, gases or liquids or other

combustibles are present. Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations. Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum space clearances from combustibles, when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the safety of this equipment and

adequate back-up controls and safety

devices must be installed. Failure to

comply could result in personal injury

and/or property damage.

Heaters must be wired by qualified

personnel in compliance with local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture

accumulation can cause fault to the

element sheath generating arcing and

releasing molten metal. Install proper

ground fault protection to prevent

personal injury and/or property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1". The standard Type 1 enclosure

is suitable for dry, indoor locations only in non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

cm

[12”

]

FIG. 1 – MOUNTING CLEARANCES

MI102 REV.7.01 Page 3 of 8

8.0 NORMAL SEQUENCE OF OPERATION
8.1
The heater must be properly mounted and wired in accordance

with these instructions, terminal cabinet door closed and secure,

fan blade free, and no obstructions to air inlet or outlet areas.

8.2 Energize the heater at the rated supply voltage.

8.3 Assuming the thermostat is calling for heat OR the thermostat

is turned to a higher temperature than ambient:

8.3.1 The main contactor(s) will energize the elements.

8.3.2 The fan motor will not start immediately.

8.3.3 After a delay of 20-50 seconds, the fan contactor will operate

and the fan will start. See paragraph 3.6 for proper fan rotation.

8.4 After the ambient temperature rises to the operating point of

the thermostat, the thermostat contact will open.

8.4.1 The main contactor(s) will de-energize the elements.

8.4.2 The fan motor will continue to operate, purging the residual

heat from the elements.

8.4.3 After a delay of 20-70 seconds, the fan contactor will open

and the fan will stop.

8.5 The cycle described in 8.3 will repeat.

9.0 MAINTENANCE
The GX unit heater is constructed to operate in tough industrial

applications with a minimum of maintenance.

However, some routine maintenance is recommended to extend

the life of the heater and its components. Always disconnect the

electrical source before performing any maintenance.
9.1 TERMINAL ENCLOSURE - At periodic intervals, of not

more than one year, open the terminal enclosure to inspect for

cleanliness and dampness. Vacuum any dust and wipe up any

moisture. Check all electrical connections and tighten if necessary.

9.2 CONTACTOR(S) - Inspect the contacts carefully and replace

the contactor(s) if excessive wear is becoming evident. Contacts

which are not pitted can be cleaned using a fine grade sandpaper

or emery cloth.

9.3 MOTOR - The motor supplied is rated at 1/3 HP with totally

enclosed construction and sealed ball bearings. These motors are

“permanently” lubricated by the manufacturer. Internal thermal

protection is provided to eliminate motor overheating. Check all

motor mounts and tighten if necessary.

9.4 FAN BLADE - Visually inspect the fan blade to ensure accidental

damage has not occurred. If bent or damaged, a factory balanced

blade should be installed so that the rated air flow is maintained. A

damaged fan blade may not deliver the required air flow over the

elements, resulting in short cycling of the internal contactors by the

high limit control. This condition will significantly shorten the life of

the contactors. Check to ensure the fan blade is tightly fastened to

the motor shaft.

9.5 HEATER PAINT FINISH - The GX unit heater is finished with

an epoxy paint to provide maximum resistance to corrosion due

to airborne contaminants. We recommend the cabinet be wiped

down periodically using a mild detergent.

8.0 SÉQUENCE NORMALE D’OPÉRATION
8.1
L’appareil doit être installé et raccordé selon les normes

recommandées pour ce type d’appareil, i.e. Porte du boîtier de

contrôle fermée et verrouillée, aucune obstruction à l’entrée et à la

sortie de l’air, et l’éventail non obstrué.

8.2 Mettez l’appareil sous tension (voir la plaque signalétique pour

tension d’opération).

8.3 En assumant que le thermostat ets en position de demande

ou que le point de consigne est plus élevé que la température

ambiante:

8.3.1 Le(s) contacteur(s) principal actionne l’opération des

éléments chauffants.

8.3.2 Le ventilateur ne partira pas immédiatement.

8.3.3 Après un délai de 20-50 secondes, le ventilateur se mettra

en marche. Voir paragraphe 3.6 pour la rotation adéquate du

ventilateur.

8.4 Dès que la température ambiante atteindra le point de consigne

du thermostat, les contacts de celui-ci s’ouvrent.

8.4.1 Le contacteur principal coupe l’opération des éléments

chauffants.

8.4.2 Le ventilateur continue de tourner jusqu’à ce que la chaleur

résiduelle de l’appareil est évacuée.

8.4.3 Après un délai de 20-70 secondes, le ventilateur s’arrêtera.

8.5 Le cycle décrit au paragraphe 8.3 reprendra.

9.0 ENTRETIEN
L’appareil GX est conçu et fabriqué pour les applications

industrielles robustes exigeant une maintenance minime.

Cependant, une maintenance routinière est recommandée

afin d’accroître la durabilité de l’appareil et de ses composants.

Débranchez toujours l’appareil avant de procéder à l’entretien.
9.1 BOÎTIER DE CONTRÔLE - À intervalles réguliers, au moins

une fois par année, ouvrez le boîtler de contrôle pour vous assurer

de la propreté et de l’étanchiété. Débarrassez de toutes poussières

et asséchez si nécessaire. Vérifiez également la fermeté des

connexions électriques.

9.2 CONTACTEUR(S) - Vérifiez les contacts soigneusement et

remplacez s’il y á usure excessive. Sinon, nettoyez les contacts en

utllisant un papier sablé fin ou linge d’émeri.

9.3 MOTEUR - Moteur de 1/3 C.V., Totalement fermé avec

roulement à billes, lubrication permanente par le manufacturier et

protection thermique intégrale. Vérifiez les points de montage et

reserrez si nécessaire.

9.4 ÉVENTAIL - Procédez à une inspection visuelle et assurez

vous que les palles ne sont pas endommagées. Si elles sont pliées

ou endommagées, remplacez par un nouvel éventail balancé

en usine afin d’obtenir le débit d’air spécifique de l’appareil. Un

éventail endommagé peut entrainer une surchauffe de l’appareil

et un cyclage répétitif de la protection haute-limite. Ce cyclage

provoquera l’usure prématurée des contacteurs. Assurez-vous

que l’éventail est ancré solidement à l’arbre du moteur.

9.5 FINI EXTÉRIEUR DE L’APPAREIL - L’appareil GX est

recouvert d’un fini “epoxy” pour vous assurer une plus grande

résistance à la corrosion due aux contaminants de l’air. Essuyez

le cabinet de l’appareil avec un détergent doux annuellement.

Advertising