Series ok3 – infrared radiant heaters – CCI Thermal Technologies GX - Heavy Duty Forced Air Unit Heater Manuel d'utilisation

Page 2

Advertising
background image

MI182 REV.8 Page 1 of 2

CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3 – INFRARED RADIANT HEATERS

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that

combustible materials are always kept at a safe distance from the radiant energy. This heater is

not intended for use in hazardous areas where flammable vapours, gases or liquids or other

combustibles are present. Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations. Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum space clearances from combustibles, when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the safety of this equipment and

adequate back-up controls and safety

devices must be installed. Failure to

comply could result in personal injury

and/or property damage.

Heaters must be wired by qualified

personnel in compliance with local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture

accumulation can cause fault to the

element sheath generating arcing and

releasing molten metal. Install proper

ground fault protection to prevent

personal injury and/or property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1". The standard Type 1 enclosure

is suitable for dry, indoor locations only in non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

cm

[12”

]

FIG. 1 – MOUNTING CLEARANCES

MI102 REV.7.01 Page 2 of 8

MI182 REV.8 Page 1 of 2

CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3 – INFRARED RADIANT HEATERS

FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that

combustible materials are always kept at a safe distance from the radiant energy. This heater is

not intended for use in hazardous areas where flammable vapours, gases or liquids or other

combustibles are present. Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations. Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion. The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage. Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum space clearances from combustibles, when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the safety of this equipment and

adequate back-up controls and safety

devices must be installed. Failure to

comply could result in personal injury

and/or property damage.

Heaters must be wired by qualified

personnel in compliance with local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply. Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation contamination or moisture

accumulation can cause fault to the

element sheath generating arcing and

releasing molten metal. Install proper

ground fault protection to prevent

personal injury and/or property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply conductors to the heater must be suitable for

110°C(230°C). The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1". The standard Type 1 enclosure

is suitable for dry, indoor locations only in non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes located at each top corner of the housing. Either chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support (slotted holes) is adequate provided that the spacing

instructions as given in 3.0 are followed. Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

cm

[12”

]

FIG. 1 – MOUNTING CLEARANCES

3.7 MOTOR ROTATION - IMPORTANT. Three phase heaters are

supplied with motors of corresponding phase. The proper motor/fan

rotation, viewed from the rear of the heater is counter clockwise,

incorrect rotation of the fan will cause the heater to overheat and

cycle on the high limit. To reverse the fan rotation, interchange two

supply voltage conductors connected to lugs L1, L2.

3.8 The schematic wiring diagram in Fig. 5 illustrates the GX unit

heater with contactor, transformer and thermostat. Some of this

equipment is optional and may not be included with your GX heater.
4.0 TEMPERATURE CONTROL
4.1
BUILT-IN THERMOSTAT - heaters with a factory installed

thermostat have all other standard controls such as contactors,

and transformers factory installed and prewired.

4.2 THERMOSTAT KIT FAT-8A - (Field installed) Install the FAT-8A

thermostat kit in accordance with the instruction sheet provided.

4.3 REMOTE LINE VOLTAGE THERMOSTAT - A remote

thermostat rated to operate as a pilot duty, inductive device on

240V is required. For proper installation and wiring of the selected

thermostat, refer to the manufacturer’s instructions. CCI Thermal

Technologies can supply appropriate thermostats.

4.4 REMOTE LOW VOLTAGE THERMOSTATS - The GX heater

can be provided with a low voltage control internally wired for

remote connection to 24V thermostats. Ensure that this control

option is installed in the GX heater before energizing a low voltage

thermostat from the heater. For proper installation and wiring of the

selected thermostat, refer to the manufacturer’s instructions. CCI

Thermal Technologies can supply low voltage thermostats for use

with GX heaters.
5.0 “FAN ONLY” FEATURE (Summer Switch)
The “fan only” feature will allow the heater to cycle in a “heat”

mode dictated by the controlling thermostat, even though the fan is

operating continuously.
5.1 Terminals are provided for remote mount of a S.P.S.T. “fan only”

switch, rated 240V 60Hz. A jumper across terminals “T2” and “T3”

is installed at the factory, and must be removed and substituted

with the remote switch leads if this feature is to be available. See

Fig. 5.

5.2 A “fan only” switch may be factory installed (optional extra)

directly in the heater.
6.0 FAN DELAY
All GX unit heaters incorporate a fan delay feature in both the “ON”

and “OFF” cycles. This is a desirable feature allowing the heater

to come to temperature before the fan operates (no cold blasts)

and to cool down in the “OFF” cycle (longer life for the control

components and motor). Delay “ON” is 20-50 seconds and delay

“OFF” is 20-70 seconds.
7.0 REMOTE ENERGY MANAGEMENT CONTROL
Remote energy management control is standard on 40 and 50kW

units. Internal power to contactor coil C2 may be interrupted and

controlled remotely by removing the jumper between terminals

“T2” and “T3”, and then connecting a passive contactor in its place.

A closed contact will allow 100% heating capacity and an open

contact will allow 50% heating capacity. See schematic wiring

diagram Fig. 5.

3.7 ROTATION DU MOTEUR - IMPORTANT. Sur tous les appareils

triphasés, les moteurs sont également triphasés. Vue de l’arrière

de l’appareil, la rotation normale de l’éventail est dans le sens

anti-horaire. Une rotation inversée entrainera l’arrêt de l’appareil

par la haute-limite. Pour corriger la rotation, interchangez deux fils

d’alimentation sur les cosses L1, L2.

3.8 Le schéme de la Fig. 5 illustre un appareil GX muni d’un

contacteur, transformateur et thermostat. Cet équipement est

facultatif et peut ne pas être inclus dans votre appareil.
4.0 CONTRÔLE DE TEMPÉRATURE
4.1
THERMOSTAT INTÉGRÉ - Les appareils avec thermostat

intégré possède tous les autres contrôles tels que contacteur et

transformateur et sont préfilés en usine.

4.2 TROUSSE DE THERMOSTAT FAT -8A - (Pour installation

en chantier) Installez le thermostat FAT-8A selon les instructions

fournies avec cette trousse.

4.3 THERMOSTAT À TENSION SECTEUR À DISTANCE - Un

thermostat à distance, adéquat pour circuit de commande et appareil

inductif à 240V ets requis. Voir les instructions du manufacturier

pour une installation adéquate. CCI Thermal Technologies

possède en magasin une gamme variée de thermostats.

4.4 THERMOSTAT À BASSE TENSION À DISTANCE - L’appareil

GX peut intégré les contrôles requis pour le raccordement à

distance d’un thermostat à 24V. Assurez-vous que ce dispositif

facultatif est intégré à l’appareil GX avant d’opérer un thermostat

à basse tension à partir de l’appareil. Voir les instructions du

manufacturier pour une installation adéquate. CCI Thermal

Technologies possèdent une gamme variée de thermostats à

basse tension.
5.0 COMMANDE DU VENTILATEUR (Interrupteur Estival)
Cette caractéristique permet à l’appareil de répondre à l’appel de

chauffage, même si l’éventail est en opération continue.
5.1 Un bornier est prévu pour l’installation à distance d’un

interrupteur du ventilateur (U.P.U.D.), 240V 60Hz. Un cavalier

est instalé en usine entre les bornes T2 et T3, lequel sera

enlevé et substitué par les fils de l’interrupteur à distance si cette

caractéristique doit être disponible. Voir Fig. 5.

5.2 Un interrupteur du ventilateur est disponible pour l’installation

intégrée en usine (facultatif moyennant un suppliment).
6.0 COMMANDE À RETARDEMENT DU VENTILATEUR
Tous les appareils GX sont munis d’une commande à retardement

du ventilateur pour la mise en marche et l’arrêt. Cette caractéristique

unique évite la projection d’air froid au démarrage et la surchauffe

à l’arrêt, d’où une meilleure durabilité des composants de contrôles

et du moteur. Le délai de mise en “marche” est de 20-50 secondes

et le délai “d’arrêt” est de 20-70 secondes.
7.0 RÉGUALTEUR CENTRAL D’ÉNERGIE À DISTANCE
Des borniers intégrés à tous les appareils de 40 et 50kW permettent

d’interrompre la puissance au contacteur C2. En enlevant le

cavalier T2, T3 à bobine du contacteur C2 et en le substituant par

un contact passif, vous réduirez do 50% la capacité de l’appareil

selon le signal de la position ouverte ou fermée commandée par le

régulateur central d’énergie à distance. Voir schéma Fig. 5.

Advertising