6replace the storage drawer, Check the appliance is gas sound, Check operation of all the burners. stick on label – La Cornue CornuFé 44 Conversion to Propane Gas Manuel d'utilisation

Page 6: Pressure testing

Advertising
background image

SERVICING - WARNING

Disconnect from electricity and gas before servicing. Check appliance is safe when you have

finished.

6

Replace the storage drawer

To replace the drawer in the range, pull the side rails fully
out.

Carefully move the drawer back between the rails and
rest it on the side rails.

At each side hold the front of the drawer and pull the
side rail forward so that the clips click into position
holding the drawer to the side rails.

Check the appliance is gas sound.

CAUTION: DO NOT USE A FLAME TO CHECK FOR
GAS LEAKS.

When using test pressures greater than 1/2 psig to
pressure test the gas supply system of the residence,
disconnect the range and individual shut-off valve from
the gas supply piping. When using test pressures of 1/2
psig or less to test the gas supply system, simply isolate
the range from the gas supply system by closing the
individual shut-off valve.

Check operation of all the burners.

Stick on label

Stick the “NOW ADJUSTED FOR LP GAS” label next to the
ratings label inside the drawer cavity to indicate the gas
the appliance is now set for.

Pressure Testing

Connect the appliance to the gas supply. Check the
appliance is gas sound.
The gas pressure can be measured at the pressure test
point on the appliance side of the pressure regulator.

For proper operation, the pressure of LP supplied to the
regulator must be between 10’’ and 13’’ of water column
(2.49 - 3.24 kPa).
When checking for proper operation of the regulator, the
inlet pressure must be at least 1’’ (0.25 kPa) greater than
the operating (manifold) pressure as given above.
The pressure regulator located at the inlet of the range
manifold must remain in the supply line regardless of
whether natural or LP gas is being used.