Troubleshooting chart – Trademark Tools AIR COMPRESSOR 2.5HP/20 GALLON Manuel d'utilisation

Page 8

Advertising
background image

TROUBLESHOOTING CHART

NOTE: Troubleshooting problems may have similar causes and solutions.

PROBLEM POSSIBLE

CAUSE

SOLUTION

Low pressure or

not enough air or

compressor does

not stop

Tank drain valve is open

Close tank drain valve.

Fittings leak

Check fittings with soapy water. Tighten or reseal leaking

fittings. DO NOT OVERTIGHTEN.

Restricted air intake

Clean or replace air filter element.

Prolonged or excessive use of
air

Decrease amount of air used.

Compressor not large

enough

Check air requirement of accessory. If it is higher than

CFM and pressure supplied by compressor, you need a

larger compressor. Most accessories are rated at 25% of

actual CFM while running continuously.

Hole in air hose

Check and replace if necessary.

Tank leaks

WARNING

Immediately replace tank. DO NOT attempt to repair.

Blown seals

Replace compressor assembly.

Valve leaks

Replace compressor assembly.

Leaking or worn piston

Replace compressor assembly.

Air leaks from

regulator, or

regulator does not

regulate pressure

Dirty or damaged

regulator internal parts

Replace regulator or internal parts.

Regulated

pressure gauge

reading drops

when air

accessory is

being used

This is normal

If pressure drops to low, adjust regulator while accessory is used.

Compressor not large

enough

Check air requirement of accessory. If it is higher than

CFM and pressure supplied by compressor, you need a

larger compressor. Most accessories are rated at 25% of

actual CFM while running continuously.

Pressure relief

valve opens

Tank pressure exceeded

normal rating pressure

Replace pressure switch.

Pressure switch stuck

Replace pressure switch.

Motor will not run

Tank pressure exceeds

preset pressure switch

limit

Motor will start automatically when tank pressure drops

below tank cut-in pressure.

Motor thermal overload

protection has tripped

Turn the air compressor off, and wait until the motor has

cooled down. However wait at least 5 minutes to make

sure the thermal overload protector has recovered.

Fuse blown or circuit

breaker tripped

Replace blown fuse or reset circuit breaker. Do not use

fuse or circuit breaker with higher rating than specified for

you branch circuit.
Check for proper fuse; "Fusetron" type T is acceptable.
Check for low voltage and proper extension cord size.
Disconnect other applications from circuit. Operate

compressor on a dedicated circuit.

Check valve is stuck open Remove and clean or replace.
Wrong wire gauge in cord

or excessive extension

cord length

Check for proper gauge and extension cord length.

Loose electrical connections

Contact authorized service center.

Paint spray on internal

motor parts

Have checked at service center. Do not operate

compressor in the paint spray area.

Possible defective motor

Contact authorized service center.

-8-

Advertising