3.0 PRE-INSTALLATION PREPARATION

Clean all ashes out of the inside of the existing appliance opening. Make sure that the chimney and appliance
are free of cracks, loose mortar, creosote deposits, blockage or other signs of deterioration. If necessary, have
any repair work done by a qualifi ed professional before installing the appliance.

Do NOT remove bricks or mortar from the appliance. In case of an outside air inlet or ash dump, fi ll with
fi berglass insulation. Adhere to minimum clearances as illustrated.

MINIMUM CLEARANCES

A

Sidewall

12” (304.8mm)

B

Mantel

16” (406.4mm)

12” (304.8mm) Projection

C

Top facing

16” (406.4mm)

D

Side facing

6” (152.4mm)

E

Hearth (front)

Canada 18” (457.2mm)

US 16” (406.4mm)

F

Hearth (side)

8” (203.2mm)

G

In front of
insert

48” (1219.2mm)

MINIMUM APPLIANCE OPENING

H

Width (rear)

23” (584.2mm)

I

Width (front)

28” (711.2mm)

J

Height (front)

22” (558.8mm)

K

Height (rear)

19” (482.6mm)

L

Depth

18” (457.2mm)

M

Hearth depth

Canada 18” (457.2mm)

US 16” (406.4mm)

N

Hearth width

46” (1168.4mm)

O

Facing width

54” (1371.6mm)

P

Facing
height

46” (1168.4mm)

Q

Mantel

46” (1168.4mm)

A

E

G

F

J

K

L

H

I

B

C

D

N

O

M

P

Q

3.1 MINIMUM CLEARANCE TO COMBUSTIBLES

HEARTH EXTENSION / FLOOR
PROTECTION:
Must be non-combustible and extend in front
of the insert 8” (203.2mm) on both sides with
a minimum thickness of .500” (12.7mm),
a thermal conductivity factor (K) 0.84 and
resistance value (R) 0.59.