4 | SAMLEX AMERICA INC.

SAMLEX AMERICA INC. | 5

SECTION 2 |

Introduction

SECTION 2 |

Introduction

The output waveform of the inverter is a Modified Sine Wave. In a Modified Sine Wave,
the voltage waveform consists of rectangular pulses that approximate sine wave pulses
of a Pure Sine Wave. The voltage rises and falls abruptly at a particular phase angle and
sits at 0 Volts for some time before changing its polarity. In a Pure Sine Wave, the voltage
rises and falls smoothly with respect to phase angle and the voltage changes its polarity
instantly when it crosses 0 Volts.

!

caution!


certain devices (few examples given below) may malfunction when powered from modi-
fied Sine Wave. check with the manufacturer of the device for suitability of powering
with modified Sine Wave:

• Devices utilizing zero voltage crossing for timing control: Some clocks used in

consumer electronic items (will not keep accurate time)

• Devices using modulation of RF signals on AC lines during zero crossing

e.g. X-10 System for Home Automation

• Devices utilizing Triac based phase control for transformer less voltage step

down e.g.:

• Small battery chargers for hand tools, flashlights, night-lights, shavers etc.
• Variable motor speed control in hand tools
• Light dimmers
• Temperature controllers e.g. Temperature Controlled Electric Blankets

• Devices using high capacitance based voltage multipliers for generating high

voltage (will create very high surge currents) e.g.:

• Photographic Strobe Lights
• Laser Printers

measuring modified Sine-Wave Voltage with a “true rms” Voltmeter

As mentioned above, Modified Sine Wave voltage is a type of square wave that has an RMS
(root Mean Square) value of 115 VAC in this inverter. A general-purpose AC voltmeter is
calibrated to accurately measure the RMS value of a Pure Sine Wave and NOT of a Modified
Sine Wave. If this general-purpose voltmeter is used to measure Modified Sine Wave volt-
age, it will indicate a lower value (96 VAC to 104 VAC). for accurately measuring the voltage
of a Modified Sine Wave, use a voltmeter which is designed to measure “True RMS Values”
like fluke 87, fluke 8060A, fluke 77 / 99, beckman 4410 etc.