16 | SAMLEX AMERICA INC.

SAMLEX AMERICA INC. | 17

operating

condition/

protection

threshold/

reason

Green

LeD (5,

power)

yeLLoW

LeD (6,

input

fault)

reD

LeD (4,

fault)

Buzzer

remedy/reset

No output due

to Over Load

Shut Down

Output power

is > Continu-

ous / Surge

Rating

ON

OFF

ON

OFF

Check starting surge rating

of load. If happens with low

power CFL or SMPS, try adding

small resistive load.

If happens when inverter

is switched ON with high

capacitance load already in ON

condition, try switching ON the

load 10 sec after the inverter

has been switched ON.

Manual Reset. Unit will latch in

shut down condition. To reset,

switch OFF the ON/OFF Switch,

wait for 3 minutes and switch

ON again.

No output due

to Ground Fault

Shut Down

Neutral or

Line con-

nected to

Ground

ON

OFF

ON

OFF

Check if there is Neutral to

Ground bond or Ground Fault.

Manual Reset. Unit will latch in

shut down condition. To reset,

switch OFF the ON/OFF Switch,

wait for 3 minutes and switch

ON again.

No output

No DC Input

Voltage due

to Blown DC

Input Fuse

OFF

OFF

OFF

OFF

Check 8A fuse in the 12V

Power Plug or in the battery

input line.

SECTION 6 |

Protections Monitoring

& Troubleshooting