Installation – Lincoln Electric IM741 RANGER 250 Manuel d'utilisation

Page 15

Advertising
background image

A-7

INSTALLATION

RANGER 250

A-7

Alimentation
240 V
60 Hz, 3 fils

COMPTEUR DE

LA COMPAGNIE

D

’É

LECTRICIT

É

240 V

120 V

120 V

CHARGE

N

BARRE

NEUTRE

TERRE

DISJONCTEUR DES
LOCAUX ET
PROTECTION CONTRE
LES SURINTENSIT

É

S

TERRE

N

NOTE : CONDUCTEUR EN CUIVRE
No 6 VOIR LE CODE DE L

’É

LECTRICIT

É

NATIONAL QUI DONNE D

AUTRES

RECOMMANDATIONS SUR LA GROSSEUR DU FIL.

240 V

CONDUCTEUR DE

MISE

À

LA TERRE

40A

240 V

DISJONCTEUR

BIPOLAIRE

L

INTENSIT

É

NOMINALE DE

L

INTERRUPTEUR BIPOLAIRE

BIDIRECTIONNEL DOIT

Ê

TRE

É

QUIVALENTE OU SUP

É

RIEURE

À

CELLE DES DISPOSITIFS DE

PROTECTION CONTRE LES
SURINTENSIT

É

S DES LOCAUX.

FICHE 50 A,
120/240 V
TYPE NEMA 14-50

PRISE 50 A, 120/240 V

CONNEXION DU RANGER 250 AU C

Â

BLAGE DES LOCAUX

AVERTISSEMENT

Seul un

é

lectricien agr

é

e et certifi

é

ayant re

ç

u la bonne formation doit connecter la machine

à

un

r

é

seau

é

lectrique des locaux. S

assurer que :

L

installation est conforme au code national de l

’é

lectricit

é

et

à

tous les autres codes d

’é

lectricit

é

applicables.

Les locaux sont isol

é

s et qu

aucun retour dans le circuit de la compagnie d

’é

lectricit

é

ne peut se pro-

duire. Certaines lois et r

è

glements stipulent que les locaux soient isol

é

s avant que la g

é

n

é

ratrice ne

soit reli

é

e aux locaux. V

é

rifier les exigences provinciales et locales.

Un interrupteur de transfert bipolaire bidirectionnel est mont

é

conjointement avec le disjoncteur bidi-

rectionnel d

intensit

é

convenable entre la sortie de la g

é

n

é

ratrice et le compteur de la compagnie

d

’é

lectricit

й

.