Installation – White Rodgers 24A06G-1 Manuel d'utilisation

Page 2

Advertising
background image

2

W

R

2-WIRE

HEATING

THERMOSTAT

TYPE 24A06 DUAL LEVEL TEMP

WHITE

BLACK

W/WHITE

STRIPE

RED

BIMETAL

HEATER #1

BIMETAL

HEATER #2

SWITCH #1

SWITCH #2

TRANSFORMER

HEATING

LOAD #1

R

E

D

B

L

A

C

K

B

L

U

E

BLACK W/RED STRIPE

RED W/BLACK STRIPE

L1

L2

LINE

L1

L2

LINE

HEATING

LOAD #2

9/32"

3 1/16"

9/16"

3 15/32"

9/32"

1 3/32"

4 15/16"

3 25/32"

9/16"

1 3/32"

2 1/8"

3/8"

7/32"

The Dual-Level Temp relay may be mounted in any position

without affecting it's performance.
It can be connected using the 1/2" male conduit hub and can

be mounted to any standard junction box or wiring compartment.

It can also be mounted using the two holes in the back of

the case. Location of the mounting holes may be simplified by

holding the control against the mounting surface and marking

the proper position for drilling the holes.

INSTALLATION

All wiring should be done in accordance with local and national electrical codes and ordinances.

If a wiring diagram is supplied with the heating equipment, fol-

low those instructions. If none is available, two diagrams are

presented which show different wiring methods for the Silent

Operator relay.

OPERATION
As the thermostat closes its contacts, bimetal heaters #1 and

#2 are energized. Approximately 45 seconds later, the warping

action of these heaters closes line voltage switches #1 and #2

to energize heating loads #1 and #2.
When the thermostat opens its contacts, bimetal heaters #1

and #2 cool for approximately 45 seconds before line voltage

switches #1 and #2 open to de-energize the heating loads.

WIRING AND OPERATION

NOTE

Use thermostat with a .4A fixed

heater, or set adjustable heater

in thermostat at .4A.

Connection Table

2-Wire Thermostat

(R & W)

Black w/White stripe and

White to terminal W. Red to

terminal R.

Power Input:

Black & Blue

Heat Load 1:

Red & L2

Heat Load 2:

Black w/Red stripe & L2

1/2" STD CONDUIT HUB

WIRINg
Line Voltage
Line Voltage Field
Low Voltage
Low Voltage Field

Fig. 2. Using Two-wire Heating Thermostat to

Operate Two Separate Heating Loads

Fig. 1. Dimensions of Type 24A06 Dual Level Temp