24A06G-1

DUAL LEVEL-TEMP

SILENT OPERATOR RELAY

(Normally Open Contacts)

INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE

INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL

INJURY AND/OR PROPERTY DAMAGE.

PRECAUTIONS

This Dual Level-Temp Silent Operator Relay is designed for con-

trolling two separate loads with a single low voltage thermostat.

It is especially suitable for use with electric heating equipment.
The Dual Level-Temp relay may be used to operate two separate

heating loads by means of a single low voltage thermostat. It

is equally well suited for use with a heating-cooling thermostat

to control heating and cooling loads alternately as in motels,

apartments, office buildings, etc.
This model Dual Level-Temp relay has a voltage input of 240

volts. Since this relay is equipped with a self-contained trans-

former, the supply voltage used must agree with the voltage

rating of the relay. This model has both an inductive and non-

inductive rating.

If in doubt about whether your wiring is millivolt, line, or low

voltage, have it inspected by a qualified heating and air con-

ditioning contractor, electrician, or someone familiar with basic

electricity and wiring.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes

and ordinances.
This control is a precision instrument, and should be handled

carefully. Rough handling or distorting components could cause

the control to malfunction.

DESCRIPTION

SPECIFICATIONS

ELECTRICAL DATA

Switch Action: Two SPST switches, normally open

Thermal: Average time delay – 45 seconds

Ambient Temperature: -20° to 120°F (-24° to 49°C)

Mounting: 1/2" conduit hub or two key slot mounting holes

Thermostat Circuit Current:

Bimetal Heater #1 (Red & White Leads) – 0.21 Amps

Bimetal Heater #2 (Red & Black with White Stripe

Leads) – 0.21 Amps

The Silent Operator relay has been carefully adjusted at the fac-

tory, and no attempt should be made to adjust them in the field.

CAUTION

!

To prevent electrical shock and/or equipment damage,

disconnect electric power to system at main fuse or

circuit breaker box until installation is complete.

WARNING

!

Do not use on circuits exceeding specified voltage.

Higher voltage will damage control and could cause

shock or fire hazard.

PART NO. 37-4165D

Replaces 37-4165C

1236

www.white-rodgers.com

www.emersonclimate.com

TYPE

NUMBER

INPUT

vOLTAGE /FREqUENCY

ELECTRICAL RATING

FOR SWITCH #1

(Red and Black Leads)

FOR SWITCH #2

(Red Striped and Black Striped Leads)

NON-INDUCTIvE

INDUCTIvE*

NON-INDUCTIvE

INDUCTIvE*

24A06G-1

240VAC, 60 Hz

25A, 6000W

12 FLA (72 LRA)

25A, 6000W

12 FLA (72 LRA)

*FLA - Full Load Amps.; LRA - Locked Rotor Amps.