Vent clearances and framing – Quadra-Fire QFP44 Manuel d'utilisation

Page 34

Advertising
background image

Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08

34

No combustible
framing to be
located within
shaded area.

1-1/2 in. (13 mm)
minimum to
perpendicular
wall.

WA

L

L

2 x 4 or
2 x 6
header

Drywall

3 in.

(76 mm)

1 in. (25 mm)

minimum

Air space clearance to
bottom and sides of
horizontal pipe must be
at least 1 in. (25 mm)

Framing should be
constructed of 2 X 4
lumber or heavier.

The center of the
framing hole is
1 in. [25 mm] above
the center of the
horizontal vent pipe.

Vent
framing
hole.

102-1/2 in.

(2604 mm)*

* Center of pipe

10 in.

(254 mm)

12 in.

(305 mm)

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:

• Between

ceiling

¿

restops

• Between wall shield ¿ restops
• Around vent system

Failure to keep insulation or other material away from
vent pipe may cause over heating and ¿ re.

8

8

Vent Clearances and Framing

B. Wall Penetration Framing

Combustible Wall Penetration

Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield ¿ restop(s). The wall shield
¿ restop maintains minimum clearances and prevents cold
air in¿ ltration.

• The opening must be framed on all four sides using the

same size framing materials as those used in the wall
construction.

• A wall shield ¿ restop is required on one side only on

interior walls. If your local inspector requires a wall shield
¿ restop on both sides, then both wall shield ¿ restops
must have a heat shield attached to them.

• See Section 10.I. for information for regarding the

installation of a horizontal termination cap.

Figure 8.2 Wall Penetration

Figure 8.1 Horizontal Venting Clearances To Combustible Materi-
als

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall
shield ¿ restop is only required on one side and no heat
shield is necessary.