Caution, Adjust gas pressure settings – Rinnai EX11C (RHFE-265FTA) Manuel d'utilisation

Page 27

Advertising
background image

Rinnai Corporation EX08C, EX11C Manual

27

1. Turn off the gas and the power supply.

2. Remove the 5 screws that hold the louver assembly

and front panel. Lift the panel straight up and then
remove it.

3. Remove two pressure point screws (1/8 NPT tap) with

3/16 Allen wrench and attach the manometer to both
pressure points. Both pressure points must be used
in order to measure the differential pressure. Ensure
that the manometer is properly calibrated.

4. Turn on the gas and power supply to the appliance.

(Press the “Set back” button after turning on the
power supply.) With the unit in the off position, press
the test switch at the top of PC board until it beeps.

5. Select the correct code for gas type and altitude using

▲ and ▼ buttons. Refer to the table below.

CAUTION

Do not touch any other areas on the PC board besides
the switches while power is supplied to the appliance.
Parts of the PC board are supplied with 120 volts AC.

CAUTION

Do not touch the areas at or near the exhaust. These
areas become very hot and could cause burns.

Natural Gas

Propane Gas

Altitude

0-2000 ft

0-610 m

2001-5200 ft

611-1585 m

5201-7700 ft

1586-2347 m

7701-10200 ft

2348-3109 m

0-2000 ft

0-610 m

2001-5200 ft

611-1585 m

5201-7700 ft

1586-2347 m

7701-10200 ft

2348-3109 m

Manifold test

pressure -

W.C. Low

0.58 in

(15 mm)

0.62 in

(16 mm)

0.70 in

(18 mm)

0.78 in

(20 mm)

0.86 in

(22 mm)

0.92 in

(24 mm)

1.04 in

(27 mm)

1.16 in

(29 mm)

Manifold test

pressure -

W.C. High

3.4 in

(86 mm)

3.6 in

(92 mm)

4.1 in

(103 mm)

3.2 in

(82 mm)

5.8 in

(147 mm)

6.2 in

(158 mm)

7.0 in

(177 mm)

5.5 in

(140 mm)

EX11C

Manifold test

pressure -

W.C. Low

0.60 in

(15 mm)

0.64 in

(16 mm)

0.72 in

(19 mm)

0.80 in

(20 mm)

1.06 in

(27 mm)

1.16 in

(29 mm)

1.28 in

(33 mm)

1.41 in

(36 mm)

Manifold test

pressure -

W.C. High

2.2 in

(56 mm)

1.9 in

(49 mm)

1.7 in

(44 mm)

1.6 in

(40 mm)

3.8 in

(95 mm)

3.3 in

(84 mm)

3.0 in

(75 mm)

2.7 in

(69 mm)

EX08C

Code

A1 / A5 *

A2 / A6 *

A3 / A7 *

A4 /A8 *

L1 / L5

L2 / L6

L3 / L7

L4 / L8

Pressure

Point

Pressure
Point

Nozzle Manifold

Test Switch

PC Board

Adjust Gas Pressure Settings

* For the EX11C with natural gas: Use A1, A2, A3, or A4 for venting up to 7 feet (2.1 m) with one elbow.

Use A5, A6, A7, or A8 for venting exceeding 7 feet (2.1 m) with one elbow.