Flue terminal clearances – Rinnai ENERGYSAVER EX22C Manuel d'utilisation

Page 19

Advertising
background image

Rinnai Corporation EX17C / EX22C Manual

19

Flue Terminal Clearances

1

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single
family dwellings and serves both dwellings.

2

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

∗For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local

installation codes and the requirements of the gas supplier.

Ref

Description Canadian

Installations US

Installations

A

Clearance above grade, veranda,
porch, deck, or balcony. (Take into
account the anticipated snow line)

12 inches (30 cm)

12 inches (30 cm)

B

Clearance to window or door that may
be opened

6 inches (15 cm) for

appliances < 10,000 BTUh;

12 inches (30 cm) for

appliances > 10,000 BTUh

and < 100,000 BTUh,

36 inches (91 cm) for

appliances > 100,000 BTUh

6 inches (15 cm) for

appliances < 10,000 BTUh;

9 inches (23 cm) for

appliances > 10,000 BTUh

and < 50,000 BTUh,

12 inches (30 cm) for

appliances > 50,000 BTUh

C

Clearance to permanently closed
window

* *

D

Vertical clearance to ventilated soffit,
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal

* *

E

Clearance to unventilated soffit

*

*

F

Clearance to outside corner

*

*

G

Clearance to inside corner

20 inches (50 cm)

20 inches (50 cm)

H

Clearance to each side of center line
extended above meter/regulator
assembly

3 feet (91 cm) within a height

15 feet (4.5 m) above the

meter/regulator assembly

*

I

Clearance to service regulator vent
outlet

3 feet (91 cm)

*

J

Clearance to nonmechanical air supply
inlet to building or the combustion air
inlet to any other appliance

6 inches (15 cm) for

appliances < 10,000 BTUh;

12 inches (30 cm) for

appliances > 10,000 BTUh

and < 100,000 BTUh,

36 inches (91 cm) for

appliances > 100,000 BTUh

6 inches (15 cm) for

appliances < 10,000 BTUh;

9 inches (23 cm) for

appliances > 10,000 BTUh

and < 50,000 BTUh,

12 inches (30 cm) for

appliances > 50,000 BTUh

K

Clearance to a mechanical air supply
inlet

6 feet (1.83 m)

3 feet (91 cm) above if within

10 feet (3 m) horizontally

L

Clearance above paved sidewalk or
paved driveway located on public
property

7 feet (2.13 m) 1 *

M

Clearance under veranda, porch, deck,
or balcony

12 inches (30 cm) to non-

flammables 2

24 inches (60 cm) to

flammables 2

12 inches (30 cm) to non-

flammables 2

24 inches (60 cm) to

flammables 2