Conversion procedure, Gain access replace components – Rinnai Rimal Energysaver Gas Direct Vent Wall RHFE-263FA II Manuel d'utilisation

Page 3

Advertising
background image



Rinnai Corporasion RHFE-263FAConversion Manual

Manifold screw locations

Conversion Procedure

The gas supply shall be shut off prior to disconnecting the electrical power, before

proceeding with the conversion.

Gain Access

Replace Components

Confirm that the inlet gas pressure is between the minimum and maximum pressures allowed for this appliance.

1. Hold both ends of the bottom cover (Undercover

assembly) and pull toward you to remove the

cover. Cover snaps in place.

2. Remove the 7 screws that hold the front panel and

the louver assembly to remove panel from the unit.

Pull the panel out at the bottom about 4 inches

(100mm) and lift up over clips that hold it in place at

the unit’s top.

3. Remove 1 screw from the bracket with the overheat

switch. Place bracket to the side out of your way.

Refer to the Technical Data and Parts List to ensure to

the correct injectors and dampers are installed.

1. Remove the 2 manifold screws. Rotate the

manifold and connecting tube to access the

injectors.

2. Replace the 2 injectors with the proper size for the

gas type to be used.

3. Remove the burner screw from the burner

assembly.

4. Replace the primary and secondary dampers with

the dampers for the gas type to be used. (Pull the

secondary damper straight out using the tab on the

side.)

5. Install the manifold (2 screws) and overheat switch

bracket (1 screw).

6. Confirm that the electrode and leads are installed.

7. Complete the procedure, Adjust Gas Pressure

Settings.

Flame view port

Electrode and leads

Primary

damper

Burner screw Secondary

damper tab

Injectors

Bracket

Bottom cover

Front panel

Louvers