Installation 17

Table 5

Connection Type / Wire Size Range

Connection Type

UPS Module

Rating

kVA

AC Input

Battery

Bypass Input

& AC Output

Neutral

Ground

10 - 30

Compression

lug

#14 to #1/0

Compression

lug

#14 to #1/0

Compression

lug

#14 to #1/0

Compression

lug

#14 to #1/0

Ground studs

3/8" - 16 x 1.00"

Lug required

40 - 50

Compression

lug

#6 to 250 kcmil

Compression

lug

#6 to 250 kcmil

Compression

lug

#6 to 250 kcmil

Natural studs

3/8" - 16 x 1.00"

Lug required

Ground studs

3/8" - 16 x 1.00"

Lug required

65 - 125

Bus bars (2” x 3-1/4”) with connecting hardware (3/8”) are provided for all power wiring

terminations. A field-supplied lug is required.

Use factory supplied connections for terminations where they are provided. Refer to Figure 16 for field-
supplied wiring termination details. Use commercially available UL listed solderless lugs for the wire size
required for your application. Connect wire to the lug using tool and procedure specified by the lug
manufacturer.

Table 6

Torque Specifications (Unless Otherwise Labeled)

Nut and Bolt Combinations

Bolt Shaft Size

Grade 2

Standard

Electrical Connections

with Belleville Washers

Lb-in

N-m

Lb-in

N-m

1/4

53

6.0

46

5.2

5/16

107

12.1

60

6.8

3/8

192

21.7

95

10.7

1/2

428

48.4

256

28.9

Terminal Block Compression Lugs

UPS Module

Rating

kVA

Wiring

Wire Size or

Range

Lb-in

N-m

10 - 125

Control

#22 - #14

3.5 to 5.3

0.4 to 0.6

10 - 30

Power

#6 - #1/0

50

5.6

40 - 50

Power

#6

250

28.2

250 kcmil

275

31.1