8 Installation

Notes

1.

Nominal (NOM) current is based on full rated output load.

2.

Maximum (MAX) current (125% of NOM) is short duration for battery recharge conditions.

3.

UPS input and bypass cables must be run in separate conduit from output cables.

4.

If the UPS module is to be upgraded in the future, it is recommended that the AC input, bypass AC input, battery, and AC output wiring and overcurrent
protection be sized initially for the future upgraded size.

5.

Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.

6.

Power cables from UPS DC link to batteries should be sized for a total maximum 2.0 volt line drop (measured at UPS) at maximum discharge current.

7.

Recommended bypass AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 220-2(a).

8.

UPS output load cables must be run in separate conduit from input and bypass cables.

9.

Minimum sized grounding conductors to be per NEC 250-95. Parity sized ground conductors are recommended. Neutral conductors to be sized for full
capacity per NEC-16 Note 10.

10. Wiring requirements:

AC INPUT: 3-phase, 3-wire plus ground (unit supplied with input isolation transformer).
3-phase, 4-wire plus ground (unit supplied with input auto transformer).
AC OUTPUT: 3-phase, 4-wire plus ground.
DC INPUT: 2-wire (positive and negative), plus ground.

11. All wiring is to be in accordance with national and local electrical codes.
12. Minimum access clearance is 3 feet front and 1 foot above UPS.
13. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size, then replace.
14. Control wiring and power wiring must be run in separate conduit.
15. Battery cabinet not included.

Additional Notes

1.

If site configuration includes a back-up emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS
application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS compatible regulator
(generator voltage regulation). Consult generator manufacturer for required generator options and sizing.

2.

If site configuration includes an automatic transfer switch, refer to the Liebert Power Line titled “Criteria for Application of Automatic Transfer Switches
(ATS) with Uninterruptible Power Supply (UPS) Systems.” 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliary
contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.

3.

If site configuration requires an external isolated maintenance bypass circuit, it should be noted that the Utility AC input is not in phase with the UPS AC
output, with the optional delta-wye input isolation transformer. Consult with sales representative or UPS applications engineer.

Table 2

Site Planning Data, Series 300 DT, Dual Input 10 to 50 kVA

Model

Power

Rating

Voltage

Rectifier

AC Input

Rectifier

AC Input

with Optional

Input Filter

Battery

AC Output

Mechanical Data

Current

Rec

**

Current

Rec

**

Nominal

Voltage

Full

Load

Max.

Dis-

charge

Current Current

Rec

**

Dimen-

sions

Weight

DFL

Lb./

Ft.

2

Heat

Dis-

sipa-

tion

BTU/

hr.

Cooling

Air

CFM

kVA kW VAC/Freq Nom Max

Nom Max

kW

Nom

(WxDxH)

312

*

10

8

208/60Hz
240/60Hz
480/60Hz
600/60Hz

35A
29A
15A
12A

44A
36A
19A
15A

60A
50A
25A
20A

30A
26A
13A
11A

37A
32A
16A
14A

50A
40A
20A
20A

204VDC

(102 cells)

9.3

58A

28A
24A
12A
10A

35A
30A
15A
15A

36x28x72 in

91x72x183 cm

1100 lbs

499 kg

157 6000

600

322

*

15

12 208/60Hz

240/60Hz
480/60Hz
600/60Hz

50A
43A
22A
18A

63A
54A
28A
23A

80A
70A
40A
30A

44A
38A
19A
15A

55A
48A
24A
19A

70A
60A
30A
25A

204VDC

(102 cells)

13.8

85A

42A
36A
18A
14A

60A
45A
25A
20A

36x28x72 in

91x72x183 cm

1100 lbs

499 kg

157 8000

600

332

*

20

16 208/60Hz

240/60Hz
480/60Hz
600/60Hz

65A
56A
28A
23A

81A
70A
35A
29A

100A

90A
50A
40A

57A
50A
25A
20A

72A
62A
31A
25A

90A
80A
40A
30A

360VDC

(180 cells)

17.8

62A

56A
48A
24A
20A

70A
60A
30A
25A

36x28x72 in

91x72x183 cm

1400 lbs

635 kg

200 8900

800

342

*

30

24 208/60Hz

240/60Hz
480/60Hz
600/60Hz

96A
83A
42A
33A

120A
104A

53A
41A

150A
125A

70A
50A

85A
74A
37A
29A

106A

92A
46A
37A

150A
110A

60A
50A

360VDC

(180 cells)

26.4

92A

83A
72A
36A
29A

125A

90A
50A
40A

36x28x72 in

91x72x183 cm

1400 lbs

635 kg

200 12300

1050

347

*

40

32 208/60Hz

240/60Hz
480/60Hz
600/60Hz

128A
111A

55A
44A

160A
139A

69A
55A

200A
175A

90A
70A

113A

98A
49A
39A

142A
123A

61A
49A

175A
150A

80A
60A

360VDC

(180 cells)

35.2

122A

111A

96A
48A
39A

150A
125A

60A
50A

36x28x72 in

91x72x183 cm

1900 lbs

862 kg

271 16400

1050

357

*

50

40 208/60Hz

240/60Hz
480/60Hz
600/60Hz

158A
137A

68A
55A

198A
171A

85A
69A

250A
225A
110A

90A

140A
122A

61A
49A

175A
152A

76A
61A

225A
200A
100A

80A

360VDC

(180 cells)

43.7

150A

139A
120A

60A
48A

175A
150A

80A
60A

36x28x72 in

91x72x183 cm

1900 lbs

862 kg

271 18700

1050

Applicable
Notes:

1

2

3,4

9,10

11
13
14

1

2

3,4

9,10

11
13
14

5

4,6

9

11
13
14

1

4,7
8,9

11
13
14

12,13,15

15

15

For explanation of Applicable Notes, see referenced numbers in Notes below.

* Field-upgradeable to next larger model
**Rec = Recommended External Overcurrent Protection
DFL = Distributed Floor Loading