Installation 9

Notes

1.

Nominal (NOM) current is based on full rated output load.

2.

Maximum (MAX) current (125% of NOM) is short duration for battery recharge conditions.

3.

UPS input and bypass cables must be run in separate conduit from output cables.

4.

If the UPS module is to be upgraded in the future, it is recommended that the AC input, bypass AC input, battery, and AC output wiring and overcurrent
protection be sized initially for the future upgraded size.

5.

Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.

6.

Power cables from UPS DC link to batteries should be sized for a total maximum 2.0 volt line drop (measured at UPS) at maximum discharge current.

7.

Recommended bypass AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 220-2(a).

8.

UPS output load cables must be run in separate conduit from input and bypass cables.

9.

Minimum sized grounding conductors to be per NEC 250-95. Parity sized ground conductors are recommended. Neutral conductors to be sized for full
capacity per NEC-16 Note 10.

10. Wiring requirements:

AC INPUT: 3-phase, 3-wire plus ground (unit supplied with input isolation transformer).
3-phase, 4-wire plus ground (unit supplied with input auto transformer).
AC OUTPUT: 3-phase, 4-wire plus ground.
DC INPUT: 2-wire (positive and negative), plus ground.

11. All wiring is to be in accordance with national and local electrical codes.
12. Minimum access clearance is 3 feet front and 1 foot above UPS.
13. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size, then replace.
14. Control wiring and power wiring must be run in separate conduit.
15. Battery cabinet not included.

Additional Notes

1.

If site configuration includes a back-up emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS
application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS compatible regulator
(generator voltage regulation). Consult generator manufacturer for required generator options and sizing.

2.

If site configuration includes an automatic transfer switch, refer to the Liebert Power Line titled “Criteria for Application of Automatic Transfer Switches
(ATS) with Uninterruptible Power Supply (UPS) Systems.” 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliary
contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.

3.

If site configuration requires an external isolated maintenance bypass circuit, it should be noted that the Utility AC input is not in phase with the UPS AC
output, with the optional delta-wye input isolation transformer. Consult with sales representative or UPS applications engineer.

Table 3

Site Planning Data, Series 300 DT, Dual Input 65 to 125 kVA

Model

Power

Rating

Voltage

Rectifier

AC Input

Rectifier

AC Input

with Optional

Input Filter

Battery

AC Output

Mechanical Data

Current

Rec

**

Current

Rec

**

Nominal

Voltage

Full

Load

Max.

Dis-

charge

Current Current

Rec

**

Dimen-

sions

Weight

DFL

Lb./

Ft.

2

Heat

Dis-

sipa-

tion

BTU/

hr.

Cooling

Air

CFM

kVA kW VAC/Freq Nom Max

Nom Max

kW

Nom

(WxDxH)

362

*

65

52 208/60Hz

240/60Hz
480/60Hz
600/60Hz

197A
171A

85A
68A

246A
214A
106A

85A

300A
300A
150A
110A

182A
158A

79A
63A

228A
197A

99A
79A

300A
250A
125A
100A

360VDC

(180 cells)

57.1

198A

180A
155A

78A
63A

225A
200A
100A

80A

54x28x72 in

137x72x183 cm

2500 lbs

1134 kg

238 24200

1200

367

75

60 208/60Hz

240/60Hz
480/60Hz
600/60Hz

234A
203A
101A

81A

293A
254A
126A
101A

400A
350A
175A
125A

208A
180A

90A
72A

260A
225A
113A

90A

350A
300A
150A
125A

360VDC

(180 cells)

65.2

225A

208A
180A

90A
72A

300A
225A
125A

90A

54x28x72 in

137x72x183 cm

2500 lbs

1134 kg

238 25400

1200

377

*

100 80 208/60Hz

240/60Hz
480/60Hz
600/60Hz

312A
270A
135A
108A

390A
338A
169A
135A

500A
450A
225A
175A

277A
240A
120A

95A

347A
300A
150A
120A

450A
400A
200A
150A

360VDC

(180 cells)

86.5

307A

278A
241A
120A

96A

350A
300A
150A
125A

54x28x72 in

137x72x183 cm

2700 lbs

1225 kg

257 33800

1600

382

125 100 208/60Hz

240/60Hz
480/60Hz
600/60Hz

386A
334A
167A
134A

483A
418A
209A
168A

600A
600A
300A
225A

343A
297A
148A
119A

429A
371A
185A
149A

600A
450A
225A
175A

360VDC

(180 cells)

108.1

383A

347A
301A
150A
120A

450A
400A
200A
150A

54x28x72 in

137x72x183 cm

2700 lbs

1225 kg

257 38000

1600

Applicable
Notes:

1

2

3,4

9,10

11
13
14

1

2

3,4

9,10

11
13
14

5

4,6

9,10

11
13
14

1

3,4,7

8,9,10

11
13
14

12,13,15

15

15

For explanation of Applicable Notes, see referenced numbers in Notes below.

* Field-upgradeable to next larger model
**Rec = Recommended External Overcurrent Protection
DFL = Distributed Floor Loading