TOOLS NEEDED FOR INSTALLATION

• Saber Saw or Jig Saw

• Drill

• 1 1/4" Wood Drill Bit

• Pliers

• Phillips Screwdriver

• Flat Blade Screwdriver

• Wire Stripper or Utility Knife

• Metal Snips

• Measuring Tape or Ruler

• Level

• Pencil

• Caulking Gun

• Duct Tape

PARTS SUPPLIED FOR INSTALLATION

• 1 Hardware Package

• 1 Literature Package

PARTS NEEDED FOR INSTALLATION

• 2 Conduit Connectors

• Power Supply Cable

• 1 Wall or Roof Cap

• All Metal Ductwork

OPTIONAL ACCESSORIES AVAILABLE

• 30" High Backsplash

30" high, mounts to the wall beneath the rangehood

for a coordinated look

part # 620000095 - 30" model

part # 620000097 - 36" model

part # 620000098 - 48" model

• Telescopic Chimney Kit (FIGURE 3)

24" wide, extends to accomodate 8 - 9 foot ceilings

part # 6097336 fits all size hoods

• Full Width Duct Cover (FIGURE 4)

12" high, extends full width of the hood

part # 6097337 - 30" model

part # 6097338 - 36" model

part # 6097339 - 48" model

• Duct Transition Kit

For 48" model only, optional kit transitions two 3 1/4"

x 10" openings to one 10" round opening

part # 6000002

• *Charcoal Filters

* it is highly recommended that professional style

cooking always be vented to the outside; for reciru-

lating installations, some ductwork is required to

exhaust the unit out of the cabinet. For 48" model,

order 2 kits, one for each motor.

part # 6093034

RANGEHOOD WITH

TELESCOPIC CHIMNEY KIT

CALCULATE THE DUCTRUN LENGTH

WARNING

Due to the weight and size of the rangehood

canopy, two or more people are needed to move

and safely install the rangehood canopy.

Failure to properly lift rangehood could result in

damage to the product or personal injury.

PERSONAL INJURY HAZARD

9 Feet Straight Duct

2 - 90˚ Elbows

Wall Cap
Total System

9.0 feet

10.0 feet

0.0 feet

19.0 feet

FIGURE 2

3.0 feet

5.0 feet

12.0 feet

0.0 feet

45˚ Elbow

90˚ Elbow

90˚ Flat Elbow

Wall Cap

FIGURE 1

PLAN THE INSTALLATION

This rangehood can be vented through the wall or ceiling. To vent through a wall,

the blower must be turned to vent to the rear. This rangehood can be installed

with two different chimney options as well as without a chimney. Before you begin

installation, you must determine which chimney installation will be used.

The Telescopic Chimney Kit is adjustable and designed to meet varying ceiling

heights from 8 to 9 feet. FIGURE 3 illustrates the dimensions of the rangehood

with the optional Telescopic Chimney Kit. FIGURE 4 illustrates the dimensions

of the rangehood with the optional Full Width Duct Cover. The body of the

rangehood is the same dimensions regardless of the chimney option used.

WARNING! BEFORE MAKING ANY CUTS OR HOLES FOR INSTALLATION,

DETERMINE WHICH VENTING METHOD AND CHIMNEY WILL BE USED AND

CAREFULLY CALCULATE ALL MEASUREMENTS.

25

"

25

"

25

"

25

"

RANGEHOOD WITH

FULL WIDTH DUCT COVER

FIGURE 3

FIGURE 4

The ductrun should not exceed 35 equivalent

feet if ducted with the required minimum of 3

1/4" by 10" rectangular duct or 55 equivalent

feet if ducted with 10" round duct (when

using Duct Transition Kit for 48” model

only). Calculate the length of the ductwork

by adding the equivalent feet in FIGURE 1 for

each piece of duct in the system An example

is given in FIGURE 2. For best results, use

no more than three 90° elbows. Make sure

that there is a minimum of 24" of straight

duct between elbows if more than one is

used. Do not install two elbows together.

If you must elbow right away, do it as far

away from the hood's exhaust opening

as possible.

!