TROUBLE

CAUSE

SOLUTION

• The heater won’t start

• Faulty electrical supply

• Check function and positioning of main switch

• Check power cord

• Check electrical connections

• Check fuses

• Wrong positioning of main switch

• Put main switch in correct position

• Wrong setting of room thermostat

• Check setting of room thermostat

• Check function of room thermostat

• Safety device (burner, thermostat L2, fan

thermal relay) not restarted after repairs

• Press the appropriate restart button:

burner (button on control device)
thermostat (button (6)
fan thermal relay (button (11)

• Thermostat L1 cuts in

(the lamp (9) light up and then it cuts down)

• The combustion chamber has overheated

• Check fuel flow

• Check position registers, draw - holes, etc.

• Remove extraneous material from air ducts and

ventilation grills

• Thermostat L2 cuts in

(warning lamp (9) lights up)

• Excessive combustion chamber over

heating

• Check as indicated above

• If fault persists contact our Service Center

• Thermal relay RM cuts in

(warning light (10) lights up)

• Fan motor current absorption is excessive

• Heater with helicoidal ventilator: remove eventual

debris preventing free flow of air on intake
and outlet. Check length of air ducts, reduce if
excessive.

• Heater with centrifugal ventilator: check setting

of transmission belt as indicated in chapter
(“CoNNeCTIoN To HoT AIR DUCTs”).

• Always check that current absorption remains below

value indicated on motor manufacturer plate

• The burner starts up, the flame doesn’t light

up and the restart light on the control device
comes on

• Burner not working correctly

• Press the restart button to turn on the heater. If

the same problem arises again call an Authorized
service Technician

• The fan doesn’t start up or starts up late

• No electrical power

• Check fuses

• Check electrical connections

• F thermostat out of order

• Check the thermostat, set it and replace it if

necessary

• Winding of motor burnt or interrupted

• Replace the fan motor

• Condenser burnt (mod. “M”)

• Replace the condenser

• Motor bearings blocked

• Replace the bearings

• The fan vibrates or makes unusual noise

• Extraneous material on fan blades

• Remove extraneous material

• Not enough air circulation

• Remove obstacles to air circulation

• Not enough heat

• Wrong burner

• Call an Authorized Service Technician