Environment and enclosure, North american hazardous location approval, Back cover – Rockwell Automation 2085-ECR Micro800 Bus Terminator Module Manuel d'utilisation

Page 2

Advertising
background image

Publication 2085-IN002A-MU-P - September 2012

PN-164984

Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.

Allen-Bradley, Rockwell Automation, Micro800 and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Environment and Enclosure

North American Hazardous Location Approva

l

1

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II
applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered
Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be
difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated
disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the
spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior
of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are required to comply with certain product safety
certifications.
In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

, for additional installation

requirements.

NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by
enclosures.

The following information applies when operating this
equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en
environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with markings
on the rating nameplate indicating the hazardous location
temperature code. When combining products within a system, the
most adverse temperature code (lowest "T" number) may be used to
help determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time of
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à
une utilisation en environnements de Classe I Division 2 Groupes A, B,
C, D dangereux et non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code de température le
plus défavorable (code de température le plus faible) peut être utilisé
pour déterminer le code de température global du système. Les
combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de
l'installation.

WARNING: EXPLOSION HAZARD

Do not disconnect equipment unless power
has been removed or the area is known to be
nonhazardous.

Do not disconnect connections to this
equipment unless power has been removed
or the area is known to be nonhazardous.
Secure any external connections that mate
to this equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.

Substitution of components may impair
suitability for Class I, Division 2.

If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.

WARNING: RISQUE D’EXPLOSION

Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.

Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.

La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.

S'assurer que l'environnement est classé non
dangereux avant de changer les piles.

1.

See the Product Certification link at

http://www.rockwellautomation.com/products/certification/

for Declaration of Conformity,

Certificates, and other certification details.

Advertising