Rockwell Automation 1756-Lx_Mx ControlLogix Controller and Memory Board Installation Instructions Manuel d'utilisation
Page 42

42 ControlLogix® Controller and Memory Board
Publication
1756-IN101J-EN-P - November 2004
The following specifications apply to all ControlLogix controllers:
Description:
Value:
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
• 0° … 60° C (32 … 140° F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
• -40° … 85° C (-40 … 185° F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
• 5% … 95% noncondensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
• 2g @ 10-500Hz
Operating Shock
IEC60068-2-27 (Test Ea, Unpackaged Shock):
• 30g
Non-Operating Shock
IEC60068-2-27 (Test Ea, Unpackaged Shock):
• 50g
Emissions
CISPR 11:
• Group 1, Class A
ESD Immunity
IEC 61000-4-2:
• 6kV contact discharges
• 8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
• 10V/m with 1kHz sine-wave 80%AM from 30MHz … 2000MHz
• 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
• 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B immunity
IEC 61000-4-4:
• ±4kV at 5kHz on power ports
• ±4kV at 5kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
• ±1kV line-line(DM) and ±2kV line-earth(CM) on AC power ports
• ±2kV line-earth(CM) on communications ports
Conducted RF Immunity
IEC 61000-4-6:
• 10Vrms with 1kHz sine-wave 80%AM from 150kHz … 80MHz