Installation continued – Garland THE SUMMIT GAS CONVECTION OVEN Manuel d'utilisation

Page 7

Advertising
background image

Part # 1955202 Rev 4 (07/13/12)

Page 7

D. Assemble the stacking pipes provided in the stacking

kit as shown in diagram. This allows both ovens

to be supplied by a single gas line. The minimum

recommended size of the a single supply line for two

stacked ovens is 1 inch (25mm). Use a pipe thread

compound that is intended for use on propane gas

piping and be sure to check for leaks before finalizing the

installation.

3/4" Union

3" Nipple

3" Nipple

90 Degree Street Elbow

90 Degree Street Elbow

20-1/2" Nipple

3/4" to 1" Bell Reducer

E. Check leveling of unit four (4) ways (using a common

carpenter’s level on the rack inside the oven).

F. Plug the cord set of each unit into a 115-Volt power

supply outlet.

G. Maintain clearance from combustibles.

CAUTION: Disconnect Both Unites from Electrical Supply

Before Servicing.

Gas Supply

The importance of the proper installation of commercial

Gas cooking Equipment cannot be over stressed. Proper

performance of the equipment is dependent, in great part,

on the compliance of the installation with the manufacturer’s

specifications. Installation must conform to local codes or, in

the absence of local codes, with the National Fuel code, ANSI

Z223.1, Natural Gas Installation code, CAN/CGA-B149.1 or the

Propane Installation Code, CAN/CGA-B149.2, as applicable.

Before assembly and connection, check gas supply.

A. The type of gas for which the unit is equipped is stamped

on the data plate located on the lower rear of the left side

panel. Connect a unit stamped “NAT” only to natural gas;

connect a unit stamped “PRO” only to propane gas.

B. If it is a new installation, have gas authorities check meter

size and piping to assure that the unit is supplied with

sufficient amount of gas pressure required to operate the

unit.

C. If it is additional or replacement equipment, have gas

authorities check pressure to make certain that existing

meter and piping will supply fuel at the unit with not

more than 1/2” water column pressure drop.

NOTE: When checking pressure be sure that all other

equipment on the same gas line is on. An internal pressure

regulator is supplied with U.S. Range Convection Ovens.

Regulator is preset to deliver gas at pressure shown on the

rating plate.

The appliance and its individual shut-off valve must be

disconnected from the gas supply piping system during any

pressure testing of that system at test pressures in excess of

1/2 PSI (3.45kPa.).

The appliance must be isolated from the gas supply piping

system by closing its individual manual shut-off valve during

any pressure testing of the gas supply piping system at test

pressures equal to or less than 1/2 PSI (3.45 kPa).

NOTE: Adequate clearance must be provided for servicing

and proper operation.

Gas Connections

The 1” NPT inlet at the rear must be considered in piping the

gas supply for double stack units or 3/4” NPT for individual

(or single deck) connections. Undersized gas supply line(s)

may restrict the gas supply and affect performance. If other

gas appliances are supplied by the same supply line, the

supply line must be sized to carry the combined volume

without causing more than 1/2” pressure drop at the

manifold of each appliance on the line at full rate.

Recommended supply pressures are 7” WC, (NAT), and 11”

WC, (PRO); ± 5%. (Must not exceed 13.8” WC[NAT], and 15”

WC[PRO]).