9

95-6578

6.1

J1-7

J1-15

J1-5

J1-13

J1-6

J1-14

J1-8

J1-16

J1-9

J1-17

J1-10

J1-18

J1-11

J1-19

J2

J1

#2

#1

#19

#22

X3302

DÉTECTEUR 1

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DÉTECTEUR 2

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DÉTECTEUR 3

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DÉTECTEUR 4

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DÉTECTEUR 5

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DÉTECTEUR 6

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DÉTECTEUR 7

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DÉTECTEUR 8

#2
#1
#19

#22

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

+24 Vcc
CIRCUIT GROUND
+290 Vcc
B1 - INPUT SIGNAL
B2 - INPUT SIGNAL
B3 - INPUT SIGNAL
B4 - INPUT SIGNAL
B5 - INPUT SIGNAL
B6 - INPUT SIGNAL
B7 - INPUT SIGNAL
B8 - INPUT SIGNAL
D1

oi DRIVER

D2

oi DRIVER

D3

oi DRIVER

D4

oi DRIVER

D5

oi DRIVER

D6

oi DRIVER

D7

oi DRIVER

D8

oi DRIVER

DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED

33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64

ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8

FIRE LOGIC “A”

FIRE LOGIC “B”

ALARM OUTPUT

EXTERNAL RESET/INHIBIT

OUTPUTS INHIBITED

FAULT OUTPUT

EXTERNAL ACCEPT

STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8

DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7

EARTH GROUND

CONTRÔLEUR R7404 AVEC STAR LOGIC

A2267

NOTE: SI LE PÔLE "-" DE L'ALIMENTATION NE PEUT PAS ÊTRE

CONNECTÉ A LA MASSE DU CHÂSSIS (TERRE), CONNECTER

UNE CAPACITÉ NON POLARISÉE DE 0,47µF 400 Vcc ENTRE J1-2 ET J2-64.

NOTE: 2,5 A SOUS 24 Vcc REQUIS POUR HUIT DÉTECTEURS.

NOTE: LES CIRCUITS DÉTECTEUR/CONTRÔLEUR SONT CONFORMES

AUX EXIGENCES DE CÂBLAGE CLASS B, STYLE 0.5

(LIGNES DE NOTIFICATION A ET C).

24

Vcc

+

62

63

64

VERS J1-2

0,47 µF / 400 Vcc
NON POLARISÉE

SYSTÈMES PROTÉGÉS CONTRE
LES DÉFAUTS DE MASSE

NOTE: NE PAS CONNECTER LE FIL "A" (#2/12) DU X3302

SUR LA BORNE J1-3 DU R7404 (290 Vcc)

N° BORNE

FONCTION

1/11

TENSION cc - (FIL "C")

2/12

TENSION cc + (FIL "A")

19

SIGNAL (FIL "B")

22

oi

(FIL "D")

IDENTIFICATION DES BORNES POUR LE X3302

AVEC SORTIE IMPULSIONS

Figure 7—Système Type, Détecteurs X3302 Câblés sur un Contrôleur R7404 avec Star Logic